BCI-I Configuration
5. Click the Save button in the lower right corner of the window. A pop-up will display indicating
6. Exit Tracer TU and disconnect the USB service plug.
7. Apply power to the HVAC equipment.

Stand-alone or BAS Operation

The control system on HVAC equipment has the ability to operate the unit as a stand-alone system
or as part of a building automation system. The BCI-I (either factory or field installed), by default,
is configured for stand-alone operation. This configuration enables the HVAC equipment to operate
prior to the commissioning of the unit into the BAS.

IntelliPak Control Configuration

The IntelliPak control system must be configured at the human interface (HI) to support unit control
from the BAS. The technician should set/verify the following configuration properties as illustrated
below. The technician should also verify that the BAS Module Comm Failure diagnostic is not
present.

BAS Unit Control

The BCI-I provides a method for a BAS to control the operation of HVAC equipment. This method
consists of BACnet objects that the BAS can access to control and monitor the status of equipment.
There are two sets of objects:
The system allows the BAS technician to define the amount of control that the BAS system will
apply to the unit. This is done by configuring the state of the Out of Service property of the output
objects. If the property is set to True, the equipment will use a corresponding local value for control.
If the property is set to False, the local value is ignored and the BAS-supplied value is used for
control. The BAS value is provided to the IntelliPak by writing to the present value property of the
corresponding output object. The factory default value for the Out of Service property of these
objects is True.
8
that changes were saved to the controller. Click OK.
1.
Configuration Menu
Configuration - Model Num Digit
BAS Communication Module
Software Revision Number:
BAS Communications:
2.
Setup Menu
Unit Control: BAS/NETWORK
3.
Diagnostics Menu
Active Diagnostic - - Auto Reset
None
Output objects; used by the BAS to provide command, setpoint, and sensor information to the
IntelliPak unit.
Input objects; provide IntelliPak status information to the BAS. See tables 3 to 11 for the list of
objects supported.
34
Installed
BACnet
18.01
Human Interface Representation
ACC-SVP01B-EN • BCI-I Integration Guide