Ip Units Configuration - Trane BCI-I Integration Manual

Bacnet communication interface for intellipak and commercial self-contained
Table of Contents

Advertisement

BCI-I Configuration
Reset to Factory Default
Factory default mode is the only mode the technician can use to set the units of measure for the
device or to scan the IntelliPak unit to create BACnet objects. The process of putting the device in
factory default mode must be run prior to executing units of measure configuration or the object
self-configuration process.
opening electrical control panel.
To reset the controller to factory default/unconfigured state:
1. Power down the unit. The IMC buss must not be active during reset.
2. Establish the connection between Tracer TU and the device. Follow the procedure,
3. From the Utilities menu, select Controller and then Controller Settings. The Controller
4. On the controller settings page there is a gray bar at the bottom with Save/Cancel buttons.
5. Click the Clear Controller button and a pop-up window will appear asking for confirmation to
6. After a few seconds a pop-up will appear confirming that the controller has been reset and

IP Units Configuration

The BCI-I supports both inch-pound and SI (metric) units of measure. The factory default units of
measure is SI. The device allows only a change of units for all objects as a whole. Mixed units of
measure is not allowed. If the controller is not in factory default state, follow the previous
procedure,
To change the units of measure in the device:
1. Establish the connection between Tracer TU and the BCI-I. Follow the
2. From the Utilities drop-down menu, select Controller and then Controller Settings. The
3. In the Device Units box of the frame, select IP units of measure radio button and then click
4. Exit Tracer TU and cycle power to the controller by disconnecting the USB plug and then
6
WARNING: Remove power from the HVAC equipment before
Session of Tracer TU and Direct Connection, " p.
Settings page appears.
Move the cursor near the left edge of the bar, keeping the cursor inside the bar. Click on this area
and a Clear Controller button will appear in the upper right portion of the page.
reset the device. Click Yes.
indicating that the controller will be rebooted. Click OK.
After the controller boots up, it will be in factory default state. The units of measure is SI (metric),
the MS/TP baud rate is 76,800, and there will be no BACnet objects present in the controller.
The controller must be in this state prior to changing the units of measure or self-configuring
the device. If using inch-pound units of measure, proceed to the next section,
Configuration, otherwise, proceed to
"Reset to Factory Default, " p.
Session of Tracer TU and Direct Connection, " p.
page contains four configuration frames that are minimized. Expand the Controller Units
frame.
Save button in the lower right corner of the window. A pop-up will display indicating that
changes were saved to the controller. Select OK.
reconnecting the plug. After the controller boots up, it will be in factory default state, the units
of measure is IP , the MS/TP baud rate is 76,800, and there will be no BACnet objects present in
the controller.
5.
"BACnet Object
Configuration.
6.
5.
ACC-SVP01B-EN • BCI-I Integration Guide
"Starting a
"IP Units
procedure,"Starting a