BCI IntelliPak Rotary Switches and LEDs
BCI IntelliPak Rotary Switches and LEDs
This section provides information about the BCI-I rotary switches and LED displays.
Rotary Switches
There are three rotary switches on the front of the BCI-I device that are used to define a three-digit
address when the BCI-I is installed on a BACnet communications network. The three-digit address
setting is the BACnet MAC address.
Note: All devices are MSTP masters with valid MAC addresses of 001 to 127 for BACnet.
Figure 1.
Setting rotary switches
Before
ADDRESS
x100
Example of before and
after setting addresses
Important:
Each device on the BACnet/MSTP link must have a unique rotary switch setting, otherwise, communication problems will occur.
12
After
x1
x10
Use a 1/8 inch
flathead screwdriver
to set rotary switches.
0
ACC-SVP01B-EN • BCI-I Integration Guide