en | Commissioning
LOGIC-SENS
The LOGIC-SENS intelligent signal processing feature can be activated or deactivated via the
diagnostic software. If the signal evaluation is switched on, LOGIC-SENS recognizes briefly
occurring disturbance variables and can thus prevent a deceptive alarm.
Detection module
Fan voltage
The standard setting fan voltage setting is 9 V. In critical applications, the fan voltage can be
set to a higher level via the diagnostic software. This increases the transport speed in the pipe
system, thus achieving faster detection in the case of longer pipe lengths.
With a fan voltage of 9 V to 10.4 V, the maximum pipe lengths are reduced to 30m for I-pipe
systems or 40 m for U and double U-pipe systems. A fan voltage of 10.5 V or higher supports
the maximum pipe length.
Detection module
Caution!
Whenever the fan voltage is changed, the FCS-320-TM automatically performs an airflow
!
initialization.
Main alarm following Fire source identification
For certain applications, it is practical to perform the alarm signaling once the fire location has
been identified. To do this, the Fire alarm after ROOM·IDENT must be activated. It is important
to remember that when this function is activated, the ROOM·IDENT function must also be
activated; otherwise, the fire location cannot be identified.
The Main alarm after ROOM IDENT function is deactivated as standard.
5
Commissioning
For inserting the detection module, refer to graphic 03, page 4 .
Notice!
The FCS-320-TM designation refers to all FCS-320-TM (FCS-320-TM-R, ) versions. Specific
references are made to differences between the individual versions.
1.
Notice!
When inserting the detection module, be aware of the mechanical coding, which protects the
device against twisting.
2020.04 | 2.0 | F.01U.123.590
LOGIC-SENS
on - off
Fan voltage
9 V-13.5 V
1 Housing base
2 Detection module
3 Jumper X4 Pin 1-2 or Pin 2-3
Insert the FCS-320-TM detection module into the pre-mounted housing base that has
been checked for correct wiring.
Quick installation guide
Conventional aspiration smoke detector
LOGIC-SENS (default)
on
Fan voltage (default)
9 V
Setting intervals
0.1 V