en | Configuration
Designation
L-
Reset+
Reset-
V+
V-
L+
L-
L+
L-
Data+
Data-
*Digital external detector alarm displays for the FCS-320-TM series must be ordered
separately.
4
Configuration
After connecting the Aspiration smoke detector to the fire panel, you can configure the
detector and the detection device.
The FCS-320-TM Aspiration smoke detector series is factory preconfigured. Check whether
this configuration is suited to the local conditions. Perform object-specific configuration
adjustments using the FAS-ASD-DIAG Diagnostic software.
Fire source identification
Notice!
The term "ROOM×IDENT" is used in the FAS‑ASD‑DIAG Diagnostic Software for identifying the
fire source.
Fire source identification is activated/deactivated using the FAS‑ASD‑DIAG Diagnostic
Software via the "Settings" screen. The "ROOM×IDENT" function is deactivated as standard.
Sensitivity
The sensitivity of the detection module can be adjusted via FAS-ASD-DIAG.
Detection module
Delay
The default delay time for the alarm threshold can be changed via the diagnostic software. The
default delay time for the alarm is set to 10 s. If the smoke level increases during operation
until it reaches the alarm threshold, the delay time starts to count down. The message is
transmitted only after the delay time has expired and the smoke level remains at its current
level. In this way, deceptive alarms due to brief strains (e.g. dust) can be prevented.
Detection module
2020.04 | 2.0 | F.01U.123.590
Terminal
Function
6a
7a
Data line connection for digital remote indicator
8a
1b
Power supply outgoing
2b
3b
Alarm zone outgoing
4b
5b
Tamper zone outgoing
6b
7b
Remote indicator bus
8b
Sensitivity
0.5-2%/m
Alarm delay
0 s – 60 s
Quick installation guide
Conventional aspiration smoke detector
Standard sensitivity
0.5 %/m
Alarm delay (default)
10 s
Bosch Sicherheitssysteme GmbH
Setting intervals
0.1 %/m
Setting intervals
1 s