6. Electrical work
Cross-sectional area of Wire for Main Power Supply and On/Off Capacities
<When power is supplied separately>
Model
Outdoor Unit
3N~380-400-415 V 50 Hz
<When power is supplied from the outdoor unit>
Model
Outdoor Unit
3N~380-400-415 V 50 Hz
*1. A breaker with at least 3.0 mm contact separation in each poles shall be provided. Use non-fuse breaker (NF) or earth leakage breaker (NV).
Total operating current of the indoor unit
F0 = 16 A or less *2
F0 = 25 A or less *2
F0 = 32 A or less *2
Apply to IEC61000-3-3 about max. permissive system impedance.
*1 The Ground-fault interrupter should support inverter circuit.
The Ground-fault interrupter should combine using of local switch or wiring breaker.
*2 Please take the larger of F1 or F2 as the value for F0.
F1 = Total operating maximum current of the indoor units × 1.2
F2 = {V1 × (Quantity of Type 1)/C} + {V1 × (Quantity of Type 2)/C} + {V1 × (Quantity of Type 3)/C} + ··· + {V1 × (Quantity of Type 16)/C}
Connect to Branch box
Indoor unit
SEZ-KD∙VAQ(L), SEZ-M∙DA(L), PCA-RP∙KAQ, PCA-M∙KA,
Type 1
SLZ-KF∙VA, SLZ-M∙FA, PLA-RP∙BA, PLA-RP∙EA, PLA-M∙EA
PEAD-RP∙JAQ(L), PEAD-M∙JA(L)
Type 2
MLZ-KA∙VA, MLZ-KP∙VF
Type 3
MSZ-FH∙VE, MSZ-GF∙VE, MSZ-SF∙VE, MSZ-EF∙VE, MSZ-SF∙VA,
Type 4
MSZ-EF∙VG
MFZ-KJ∙VE2, MSZ-LN∙VG, MSZ-AP∙VG, MSZ-AP∙VF
Type 5
Type 6
Branch box
Connect to Connection kit (PAC-LV11M)
Indoor unit
MSZ-EF∙VE, MSZ-SF∙VA, MSZ-SF∙VE, MSZ-FH∙VE, MSZ-EF∙VG
Type 7
MFZ-KJ∙VE2, MSZ-LN∙VG, MSZ-AP∙VG, MSZ-AP∙VF
Type 8
Type 9
Connection kit (PAC-LV11M)
Indoor unit
Type 10 PEFY-P∙VMA(L)-E, PEFY-P∙VMA3-E
Type 11 -
PMFY-P∙VBM-E, PLFY-P∙VBM-E, PEFY-P∙VMS1-E, PCFY-P∙VKM-E,
PKFY-P∙VHM-E, PKFY-P∙VKM-E, PLFY-P∙VEM-E, PLFY-EP∙VEM-E,
Type 12
PLFY-P∙VFM-E, PFFY-VKM-E2, PFFY-VLRMM-E, PKFY-VLM-E
Type 13 PEFY-VMA(L)-E3
Type 14 PEFY-P∙VMH(S)-E
Type 15 PKFY-P∙VBM-E
PLFY-P∙VLMD-E, PEFY-P∙VMR-E-L/R, PEFY-P∙VMH-E-F,
PDFY-P∙VM-E, PFFY-P∙VLEM-E, GUF-∙RD(H)4, PEFY-VMH-E,
Type 16
PFFY-VLRM-E
C : Multiple of tripping current at tripping time 0.01s
Please pick up "C" from the tripping characteristic of the breaker.
<Example of "F2" calculation>
* Condition PLFY-P∙VBM-E × 4 + PEFY-VMA-E × 1, C = 8 (refer to right sample chart)
F2 = 19.8 × 4/8 + 38 × 1/8
= 14.65
→ 16 A breaker (Tripping current = 8 × 16 A at 0.01 s)
* 3 Current sensitivity is calculated using the following formula.
G1 = V2 × (Quantity of Type 1) + V2 × (Quantity of Type 2) + V2 × (Quantity of Type 3) + ··· + V2 × (Quantity of Type 16)
+ V3 × (Wire length [km])
G1
Current sensitivity
30 or less
30 mA 0.1 sec or less
100 or less
100 mA 0.1 sec or less
Wire thickness
V3
1.5 mm
2
48
2.5 mm
2
56
4.0 mm
2
66
1. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when proceeding with the wiring and connections.
2. The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker consideration of voltage drops.
Make sure the power-supply voltage does not drop more than 10%.
3. Specific wiring requirements should adhere to the wiring regulations of the region.
4. Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (design 60245 IEC57). For example,
use wiring such as YZW.
5. Install an earth longer than other cables.
Minimum Wire Cross-sectional area (mm
Power Supply
Main Cable
2.5
Minimum Wire Cross-sectional area (mm
Power Supply
Main Cable
4.0
Minimum wire thickness (mm
Main Cable
Branch
1.5
1.5
2.5
2.5
4.0
4.0
2
)
Breaker for Wiring *1
Ground
2.5
2
)
Breaker for Wiring *1
Ground
4.0
2
)
Ground-fault interruper *1
Ground
1.5
20 A current sensitivity *3
2.5
30 A current sensitivity *3
4.0
40 A current sensitivity *3
V1
V2
19.8
26.9
9.9
2.4
6.8
7.4
5.1
3.0
V1
V2
6.8
7.4
2.4
3.5
V1
V2
38.0
1.6
-
-
19.8
2.4
18.6
3.0
13.8
4.8
3.5
2.4
0.0
0.0
Breaker for Current Leakage
25 A
25 A 30 mA 0.1 sec. or less
Breaker for Current Leakage
32 A
32 A 30 mA 0.1 sec. or less
Local switch (A)
Breaker for wiring
(NFB)
Capacity
Fuse
16
16
25
25
32
32
Sample chart
6000
600
SAMPLE
60
10
1
0.1
0.01
1
2
3
4
6
8
C
Rated Tripping current (x)
20
30
40
en
10
20
16