Trane CAUC-C80 Installation Operation & Maintenance page 27

Remote air cooled condensers
Table of Contents

Advertisement

Table 5-4
Liquid Line & Drier Refrigerant Requirements
Liquid
Liquid
Sporlan
Line
Line
O.D.
Charge
5/8"
1.827
C-305-S
3/4"
2.728
C-307-S
C-417-S
7/8"
3.790
C-307-S
C-417-S
1-1/8"
6.461
C-419-S
Note: Refrigerant charge given in ounces per foot.
Table 5-5
Sample Operator's Maintenance Log
Current
Ambient Compr. Suct.
Temp.
Oil
Press. Press. Press.
Date
(F)
Level (Psig) (Psig) (Psig)
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
Note: Check and record the data requested above each month during the cooling season with the unit running.
Drier
Part
Refrigerant
No.
Charge
1 lb. - 1 oz.
1 lb. - 1 oz.
1 lb. - 8 oz.
1 lb. - 1 oz.
1 lb. - 8 oz.
1 lb. - 8 oz.
Refrigerant Circuit #1
Disch. Liquid Super- Sub- Compr. Suct.
heat
(F)
System Start-Up (Continued)
Refrigerant Circuit #2
Disch. Liquid Super- Sub-
cool.
Oil
Press. Press. Press.
(F)
Level (Psig) (Psig) (Psig)
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
- ok
- low
27
heat
cool.
(F)
(F)