Daiichi Electronics SQLC-110L Instruction Manual page 59

Power line super multi-meter hardware model g
Hide thumbs Also See for SQLC-110L:
Table of Contents

Advertisement

(3) 331 Analog output specification setting 【With analog output (DC0‐5V or DC1‐5V)】
Set the specification of analog output (DC0‐5V/DC1‐5V).
Selection by + and - , set value is updated by SET .
Default setting:DC1‐5V or DC0‐5V (Designation)
0‐5V
<Note> This setting does not exist at the time of an
analog output insulation product.
(4) 341 to 348 Analog output adjustment 【With analog output】
The bias and span of each analog output are adjusted.
341
Ao1 BIAS
adjustment
RESET/
SHIFT
348
Ao4 SPAN
adjustment
◆ 341 AO (Analog output) 1 bias adjustment,
343 AO (Analog output) 2 bias adjustment,
345 AO (Analog output) 3 bias adjustment,
347 AO (Analog output) 4 bias adjustment.
The bias of each analog output is adjusted.
Setting range:±10.0% (0.1% step)
Selection by + and - , set value is updated by SET .
◆ 342 AO (Analog output) 1 span adjustment,
344 AO (Analog output) 2 span adjustment,
346 AO (Analog output) 3 span adjustment,
348 AO (Analog output) 4 span adjustment.
The span of each analog output is adjusted.
Setting range:±10.0% (0.1% step)
Selection by + and - , set value is updated by SET .
1‐5V
342
RESET/
Ao1 SPAN
SHIFT
adjustment
347
RESET/
Ao4 BIAS
SHIFT
adjustment
New setting
Now setting
Setting No.
Setting factor
343
RESET/
Ao2 BIAS
SHIFT
adjustment
346
RESET/
Ao3 SPAN
SHIFT
adjustment
58
Analog output specification
344
RESET/
Ao2 SPAN
SHIFT
adjustment
RESET/
345
RESET/
Ao3 BIAS
SHIFT
adjustment
Ao1 span adjustment
SQLC-218-090
SHIFT

Hide quick links:

Advertisement

Table of Contents
loading