GE SPEEDTRONIC Mark V Troubleshooting Chart page 6

Annunciator for gas turbine

Advertisement

Alarm 1
123
L3SMT
124
L83DT1
125
L48DSX
126
L2DWZ2
127
L4DT
128
L4DEY_ALM
129
L63QDN_ALM
130
L26DWH_ALM
131
L86CRTX
132
L49CR_ALM
133
L4CRT
134
L30HRX1
135
L30HRX2
136
L49HR1A_ALM
137
L30CD
138
L30WC_LAG
139
L71WL_ALM
6
SPEEDTRONIC Mark V Annunciator Troubleshooting Chart
Starting Device Trip
The turbine has been
tripped because the start-
ing device has failed to
start the turbine.
Diesel Test Mode
Indication that diesel test
Selected
pushbutton permissive has
been activated.
Diesel Failure to Start
Diesel has failure to start.
Diesel Failure to Break
Diesel was unable to ac-
Turbine Away
celerate to maximum rpm.
Starting Device Lockout
Diesel Failure to Stop
Diesel should stop auto-
matically after a 5 minute
cooldown period.
Diesel Lube Oil
Diesel lube oil pressure is
Pressure Low
low.
Diesel Engine Cooling Wa-
Diesel cooling water tem-
ter Temp High
perature is high.
Starting Motor Protective
Cranking motor circuit
Lockout
electrical fault.
Starting Motor Overload
Starting motor is showing
an overload.
Starting Motor Breaker Did
Starting motor did not
Not Pick Up
start.
Ratchet Trouble
Ratchet did not complete a
prescribed motion in nor-
mal time.
Ratchet Did Not Start
Ratchet did not initiate a
ratchet stroke in the pre-
scribed time.
Ratchet Motor Overload
Ratchet motor overload.
Cooldown Trouble
Unit failed to go on cool-
down, or the cooldown
cycle was aborted prior to
cooldown timer timeout.
Standby Cooling Water
Either low cooling water
Pump Running
pressure, or a problem
with the main cooling wa-
ter pump.
Cooling Water Level Low
Cooling water tank level
low.
Note where in the start sequence the turbine
tripped to aid in determining cause of trip.
Check the suspect system.
Test mode should be deselected once the
test is complete.
Check diesel fuel tank.
Check diesel. Check diesel maximum
torque solenoid.
Check diesel stop solenoid 20DV.
Check diesel lube oil system.
Check diesel cooling water system.
Clear fault and reset 88CR.
Investigate starting motor circuits.
Checking starting motor module in PECC.
Check for proper operation of ratchet mech-
anism.
Check ratchet permissives.
Check ratchet motor overload (MCC).
Check for proper operation of ratchet mech-
anism.
Check ratchet system. Monitor vibration
when cooldown cycle is reinitiated.
Investigate problem with cooling water sys-
tem or main cooling water pump.
Check cooling water system for leaks.