Download Print this page

GE SPEEDTRONIC Mark V Troubleshooting Chart page 24

Annunciator for gas turbine

Advertisement

Alarm 1
453
L39VS_A_ALM
454
L39VS_D_ALM
455
L4BT_ALM
456
L4FK_ALM
457
L45FE20A_ALM Warning–Smoke Alarm
458
L45FP22A_ALM
459
L45FG24A_ALM Warning Smoke Alarm
460
L63AD4L_ALM
461
L63CT_ALM
24
SPEEDTRONIC Mark V Annunciator Troubleshooting Chart
Bently Nevada Monitor
Increased Vibrations
Alarm
Bently Nevada Monitor
Increased Vibrations
Danger
Standby Turb Compert-
Lead Fan Failed To Oper-
ment Cooling Fan RU
ate
Lead / Lag Fan Trouble
Fire Or Electrical Compo-
GAC!!
nent Failure
Warning Smoke Alarm
Fire Or Electrical Compo-
PEECC!!!!!
nent Failure
Fire Or Electrical Compo-
Generator !!!!!!
nent Failure In Gen Col-
lector Compartment
APU Low Air Pressure
Insufficicent Air Available
Alarm
Abnormal Pressure CO2
Pressure Exceeded Device
Setting
Check Shaft Vibrations
Check Bently Nevada Monitor System
Check GE Vibration Probes
Check Shaft Vibrations
Check Bently Nevada Monitor System
Check GE Vibration Probes
Check Lead Fan Control Circuit Thermostat
etc.
Investigate
Investigate
Investigate
Check APU Unit
Investigate CO2 System
GE Power Systems
General Electric Company
One River Road, Schenectady, NY 12345
518 385 2211 TX: 145354

Advertisement