Breaker Weights And Fuse Ratings - GE WavePro LVPCB Application Manual

Low voltage power circuit breakers
Table of Contents

Advertisement

Weights of WavePro™ drawout low voltage power circuit breakers and associated drawout fuse carriages (fuse roll-out ele-
ment) are shown in Table 32.1.
Table 32.1 WavePro breaker and fuse roll-out weights
Device
WPS / WPH-08
WPX-08
WPF-08
WPS / WPH-16
WPF-16
WPS-20
WPS / WPH / WPX-32
WPS / WPX-40
WPS / WPX-50
2000/3200A Fuse Roll-out (WP32FRE)
4000A Fuse Roll-out (WP40FRE)
5000A Fuse Roll-out (WP50FRE)
Table 32.2 shows the minimum and maximum fuse ratings allowed for WavePro breakers based on the breaker frame size
and rating plug. Maximum fuse ratings protect the circuit breaker under short circuit conditions with up to 200kA available.
Minimum fuse sizes are established based on UL continuous current tests when the fuse is mounted on the circuit breaker.
Table 32.2 Allowable current limiting fuse sizes for WavePro low voltage power circuit breakers (600VAC max., 50/60 Hz)
Breaker Type
Frame Size
WPF-08
800A
WPF-16
1600A
WPS-20
2000A
WPS-32
3200A
WPS-40
4000A
WPS-50
5000A
* These fuse sizes are also available as "Welder Limiters."
Class L fuses less than 800A are not UL or CSA listed. Use Class J fuses for 600A and below. The maximum fuse rating is the largest fuse that tests show
will result in proper performance of the breaker and fuse in combination under short-circuit conditions. Only Ferraz-Shawmut fuses should be used
for proper coordination.
Fuses are mounted in a separate roll-out element (fuses shipped as "XS" material).
Integrally fused 1600A frame breakers (WPF-16) equipped with 2500A fuses can be furnished with rating plugs from 300-1600A. Breakers equipped with
2500A fuses cannot be modified to accept lower rated fuses. WPF-16 breakers equipped with 2000A and lower fuses cannot be upgraded to 2500A fuses.
The maximum trip rating for a WPF-16 breaker is 1200A when furnished with other than 2500A fuses (see chart for min-max fuse rating for each rating
plug value). 2500A fuses preclude the use of shutters in the breaker cubicle.
32
Net Weight, lb. [kg]
Manual
Electrical
175 [79]
180 [82]
210 [95]
215 [98]
220 [100]
225 [102]
210 [95]
215 [98]
280 [127]
285 [129]
220 [100]
225 [102]
490 [222]
500 [227]
535 [243]
545 [247]
600 [272]
610 [277]
330 [150]
3 Fuses – add 75 [34]
335 [152]
3 Fuses – add 90 [41]
345 [156]
3 Fuses – add 90 [41]
Sensor Rating
Rating Plug
Below 150A
150A
150A
225A
300A
400A
400A
600A
700A
800A
800A
400A and below
500A
600A
700A
800A
800A
1000A
1200A
1600A
1600A
2000A
2000A and below
3200A
3200A and below
4000A
4000A and below
5000A
5000A and below

Breaker Weights and Fuse Ratings

Ferraz-Shawmut Fuse Range
300 / 350 / 400 / 450 / 500 / 600 /
800* / 1000* / 1200 / 1600*A
400 / 450 / 500 / 600 / 800* / 1000* / 1200 / 1600*A
600 / 800* / 1000* / 1200 / 1600*A
800* / 1000* / 1200 / 1600*A
450 / 500 / 600 / 800* / 1000* / 1200 / 1600* / 2000* / 2500A
500 / 600 / 800* / 1000* / 1200 / 1600* / 2000* / 2500A
600 / 800* / 1000* / 1200 / 1600* / 2000* / 2500A
800* / 1000* / 1200 / 1600* / 2000* / 2500A
1000* / 1200 / 1600* / 2000* / 2500A
2000 / 2500 / 3000 / 4000A
2000 / 2500 / 3000 / 4000 / 5000A
1000* / 1200 / 1600*A
1600* / 2000* / 2500A
2500A