2. Press key to activate the selection level.
The red LED blinks according to the following pattern:
...
...
3. Press key again to assign the current position to the 4 mA signal.
The red LED illuminates for one second. The position transmitter returns to menu item 3.
The green LED blinks according to the following pattern:
...
4. Press key four times to return to the normal state.
The green LED is constantly illuminated when the procedure is completed.
7.2.1
Determining the position at 20 mA
The second position is assigned to the 20 mA signal.
1. Press key four times to select menu item 4.
The green LED blinks according to the following pattern:
...
2. Press key to activate the selection level.
The red LED blinks according to the following pattern:
...
...
3. Press key again to assign the current position to the 20 mA signal.
The red LED illuminates for one second. The position transmitter returns to menu item 4.
The green LED blinks according to the following pattern:
...
4. Press key three times to return to the normal state.
The green LED is constantly illuminated when the procedure is completed.
EB 4749 EN
...
...
...
Start-up
7-3