The HCN is a strong irritant to eyes and respiratory system. Inhalation may cause effects on the cellular respira-
tion, resulting in convulsions and unconsciousness. Exposure to 300ppm for 2 minutes may result in death.
SE137EN has a sensor that can detect Nitric oxide (NO) gas which is a toxic and colourless, heavy as air (its den-
sity as to air is 1.04). His TWA (Time-Weighted Average) and STEL (Short Term Exposure Limit) are 25 ppm. NO is a strong
oxidant and reacts with combustible and reducing materials. On contact with the air turns it into nitrogen dioxide
(NO
). Nitric oxide is irritating to eyes and respiratory tract. Inhalation can cause pulmonary edema, may also have
2
effects on the blood, causing the formation of metaemoglobina. In more severe cases it can lead to death. Nitric ox-
ide is a pollutant that is generated in part in combustion processes, in part by natural emissions, fires or civil activi-
ties and industrial processes involving combustion, (diesel engine, gasoline, LPG, production of heat and electricity etc.).
SE137EN2 has a sensor that can detect Nitrogen dioxide (NO
characteristic sharp, biting odour, heavier than air (its density has to air is 1.58). His TWA (Time-Weighted Average) is 3
ppm and STEL (Short Term Exposure Limit) is 5 ppm. NO
NO
is formed in most combustion processes using air as the oxidant. At elevated temperatures nitrogen combines
2
with oxygen to form nitrogen dioxide. The most important sources of NO
plants, heating and vehicles, especially diesel engines). NO
lungs, pulmonary edema and death as it is capable of combining with the haemoglobin by changing the chemical
and physiological, forming metaemoglobina which is no longer able to carry oxygen to the tissues. Also, low con-
centrations (4 ppm) will anesthetize the nose.
SE137EHCL has a sensor that can detect Hydrogen cloride (HCL) (synonymous with Hydrogen chloride, muriatic acid)
which is normally a liquid, which releases a toxic gas, colorless with a pungent odor, heavier than air (its density has
to air is 1.3). His TWA (Time-Weighted Average) is 5 ppm and STEL (Short Term Exposure Limit) is 10 ppm.
This gas, In aqueous solution becomes one of the most corrosive liquids. The vapors are corrosive to eyes, the
skin and the respiratory tract. Inhalation of high gas concentrations may cause pneumonitis and pulmonary edema.
SE137ECL has a sensor that can detect Clorine (CL
odor, is extremely poisonous and heavier than air (its density has to air is 2.5). His TWA (Time-Weighted Average) is 0.5
ppm and STEL (Short Term Exposure Limit) is 1 ppm. This gas, In aqueous solution becomes a corrosive acid. The
vapors are corrosive to eyes, skin and the respiratory tract. Inhalation of the gas may cause pneumonitis and pul-
monary edema. Prolonged exposure can cause death.

OPERATIONAL DESCRIPTION

The electrochemical sensor is temperature compensated, but is sensitive to extreme humidity variations. The cali-
bration is carried out with specific gas to be detected. Anyway, it can contemporaneously detect other gases that
should be present in the same environment as listed in
Note that the Led are not visible when the enclosure is closed.
Preheating: when powered, the sensor needs a time of preliminary heating of about 60 seconds. During this peri-
od the yellow LED "FAULT" flashes. After this period, the yellow LED light off, the green LED "ON" illuminates to in-
dicate normal functioning. After this period the unit is able to detect gas even if it attains the optimum stability con-
ditions after about 4 hours continual functioning.
Normal operation: the green LED "ON" should be light on.
ALARMS: different alarms levels, depending on the models, can be set by Dip-Switch
are two different alarm methods, the normal one, will activate the corresponding relays after a fixed delay, the ad-
vanced one, operate with TLV-TWA, STEL and C value, in this case the relays will activate without delay.
The 1st red Led (ALARM 1) illuminates when the gas concentration attains 1st alarm level. Under normal alarm
method, after about 12 seconds the "ALARM 1" relay will activate, while under advanced one, with TLV-TWA level
selected, the relay will activate without delay.
The 2nd red Led (ALARM 2) illuminates when the gas concentration attains 2nd alarm level and after about 30
seconds, the "ALARM 2" relay will activate or without delay when TLV-STEL level is selected.
The 3rd red Led (ALARM 3) illuminates when the gas concentration attains 3rd alarm level and after about 60
seconds, the "ALARM 3" relay will activate or without delay when TLV-C level is selected.
TLV (Threshold Limit Values) are defined as an exposure limit to which it is believed nearly all workers can be exposed
day after day for a working lifetime without ill effect.
TLV-TWA (Threshold Limit Value–Time-Weighted Average) is the time-weighted average concentration for a conventional
8-hour workday and a 40-hour workweek, to which it is believed that nearly all workers may be repeatedly exposed,
day after day, without adverse effect.
TLV-STEL (Threshold Limit Value–Short-Term Exposure Limit) is the concentration to which it is believed that workers can
be exposed continuously for a short period of time without suffering from irritation, chronic or irreversible tissue
damage, or narcosis. STEL is defined as a 15-minute TWA exposure, which should not be exceeded at any time
during a workday.
TLV-C (Threshold Limit Value-Ceiling) is the concentration that should not be exceeded during any part of the working exposure.
The values are recommending exposure levels that are protective to workers, OSHA (Occupational Safety and Health
Administration, of the U.S. Department of Labour) and COSHH (Control Of Substances Hazardous to Health in Europe).
Faults: the instrument signal different kind of failures, as listed below. The yellow Led illuminates, the "S" output
falls down to 0mA and the "FAULT" normally activated relay deactivate. This relay, if necessary, can be used both to
signal remotely an occurred damage and to signal the absence of power to the instrument.
Yellow Led illuminates each 4 seconds (with green Led activate): this happens when the "Cartridge Sensor" has
overcome its theoretical period of life and its correct operation is not longer guaranteed. The detector keeps on op-
TECNOCONTROL S.r.l. - Via Miglioli, 47 20090 SEGRATE (MI)
Istruzione / User's Manual / Manuel d'utilisation
combined with water turns into nitric acid and nitric oxide.
2
is toxic by inhalation, it can cause irreversible damage to the
2
) which is a yellow-green gas that has a distinctive strong
2
tables 3 and
) gas which is a reddish-brown toxic gas with a
2
are internal combustion engines (power
2
4.
(see tables 2 and
Tel. +39 02 26922890 - Fax +39 02 2133734
Pag. 9/20
5÷11). There

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents