en | Smoke and heat detector installation
<610 mm
(24 in)
Figure 5.3: Detector location for slope/peak ceilings
Flat ceilings have a height less than 610 mm (24 in):
Figure 5.4: Flat ceiling definition
5.1.5

Wall mounting

If ceiling mounting is not possible because of closely spaced beams, obstructions or ceiling
material issues, then mount the smoke detector on a wall.
A correct smoke detector mounting on a wall must adhere to the following:
5.2

Installation procedure

1.
2.
3.
2020.06 | 03 | F.01U.361.555
Within 610 mm (24 in) of the peak (measured vertically) on sloping or peaked ceilings.
<610mm (24 in)
top of the detection element is between 150 mm (6 in) and 305 mm (12 in) below the
ceiling
bottom of the detection element is above the level of any door openings
Select a location preferably on a ceiling or if not possible, a wall location.
Remove the mounting plate from the detector.
Place the mounting plate on the ceiling or wall where you want to mount the detector.
With a pencil, mark the location of the 2 screw holes.