6.3 Calibration of safety components

Any work on the unit must be carried out by qualified authorised personnel. Incorrect calibration values can
cause serious damage to the unit and harm people.
The control and safety equipment is calibrated and tested in the factory before the unit is shipped.
However, after the unit has been started, the safety devices must be checked (only the high and low pressure switches).
The checks must be carried out as described in the "Periodic checks" chapter.
The calibration values are shown in the table
Control and safety components
High-pressure switch
Low pressure switch (if any)
High pressure safety valve
44
Translation from original instructions
Activation set point
37,8 barg
4,5 barg
42 barg
Differential
10,8 barg
1,5 barg
-
We reserve the right to make changes without any prior notice.
Reset
Manual
Automatic
-