Smoke detector
Info
Instructions for Installation
Smoke detector
Product characteristics at a glance
Battery-operated smoke detector with photoelectric scattered light principle
Automatic self test of the smoke evaluation
Ability to link up to 40 smoke detectors
Loud, pulsing warning signal at approx. 85 dB (A)
Battery change indicator
Contamination/disturbance indicator
Integrated test button for testing the function
Battery compartment check: if no battery is installed in the smoke detector, it cannot be locked into
the socket
Polarity reversal protection: the device cannot be destroyed due to incorrect battery connection
VdS-recognition: G 200 121
Safety Indications
Never paint over the smoke detector.
Smoke detectors only detect the smoke of a fire, but not the flames themselves.
Smoke detectors do not extinguish a fire. When the alarm sounds, search for the source of the fire
and call the fire department if necessary.
Do not use rechargeable batteries (accumulators) or power packs for power supply. They can
cause disruptions or the premature failure of the device.
The smoke detector produces a very loud and shrill sound, which can damage hearing. For this
reason, please observe a safety distance of 50 cm during the function test.
The smoke detector only monitors a defined area in the vicinity of the installation site. Install
enough detectors to cover the entire living area and ensure optimum protection.
People under the influence of alcohol or drugs may not be awakened by the signal sound.
Installation site
Smoke detectors should preferably be installed outside the door of or in bedrooms so that you will be
awakened by the smoke alarm at night. In buildings with several floors, at least one smoke detector
should be located on each floor.
The smoke detector will have optimum detection characteristics if it is installed under the ceiling in the
center of the room. If this is not possible, keep a distance of at least 50 cm from the wall.
If the smoke detector is installed in the kitchen, you should locate the device as far away from the
cooking zone as possible to prevent false alarms due to steam.
In large houses, you should use several, linked smoke detectors to cover the entire living area. If
smoke is detected by one smoke detector, it sets off an alarm and activates all connected smoke
detectors, which then also sound the alarm. Thus, you will be awakened during the night by your
linked smoke detector in the bedroom if the smoke detector in the cellar detects smoke.
Smoke detector
45/00
Art. Nr.: 0869 00 / 04
Seite: 1 von 5

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 0869 00/04 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Gira 0869 00/04

  • Page 1 GIRA Smoke detector Info Instructions for Installation Smoke detector Art. Nr.: 0869 00 / 04 Product characteristics at a glance • Battery-operated smoke detector with photoelectric scattered light principle • Automatic self test of the smoke evaluation • Ability to link up to 40 smoke detectors •...
  • Page 2: Unsuitable Installation Sites

    GIRA Smoke detector Info Instructions for Installation Unsuitable installation sites In order to prevent false alarms and malfunctions, do not install the smoke detector: • in rooms where a large amount of steam, dust, or smoke are produced under normal circumstances.
  • Page 3 Instructions for Installation Linking smoke detectors You can link up to 40 Gira smoke detectors with one another. The connection of the detectors is achieved parallel with a two-core cable (e.g. telephone cable: J-Y(St)Y 2x2x0.6 mm). The total cable length of the detector network may not exceed 450 m.
  • Page 4: Operating And Alarm Signals

    GIRA Smoke detector Info Instructions for Installation Operating and alarm signals Signal Meaning Signal sound Light diode Loud intermittent sound Blinks Local smoke alarm Smoke alarm to linked smoke Loud intermittent sound — detector Short signal sound at 45 sec.
  • Page 5: Technical Data

    Gira Giersiepen GmbH & Co. KG Postfach 1220 D-42461 Radevormwald Telefon: +49 / 21 95 / 602 - 0 Telefax: +49 / 21 95 / 602 - 339 Internet: www.gira.de Smoke detector 45/00 Seite: 5 von 5...

Table of Contents