230 v base for smoke alarm device dual

Advertisement

Quick Links

Installation and operating
EN
instructions
230 V base for
smoke alarm device
Dual
2331 02
For your safety
Installation and mounting of electrical
devices may only be carried out by
qualified electricians.
Serious injury (e.g. caused by an electric
shock), fire, or material damage are
possible in case of improper mounting.
Read these instructions thoroughly and
observe them.
These instructions are part of the product
and must remain with the end customer.
Product features
The 230 V base supplies mains voltage of
230 V to the smoke alarm device Dual Q.
The battery integrated in the smoke alarm
device Dual Q then only supplies power in
case of a mains failure.
Product features
• Base with integrated power supply unit
for power supply of the smoke alarm
device Dual Q with 230 V AC.
• Can also be used for the smoke alarm
device Dual/VdS.
• Up to 40 smoke alarm devices can be
networked via a separate conductor.
• Connection of the supply cable/
networking cable is in the base.
• Automatic changeover to battery supply
if the mains voltage fails.
Smoke alarm device Dual Q
Please see the installation and operating
instructions of the smoke alarm device
Dual Q for all the functions of the smoke
alarm device Dual Q (e. g. switching off
smoke detection, function test, etc.).
Device description
1
1
230 V base
2
Cable inlet (pre-perforated)
3
LED display (green): 230 V mains voltage
Mounting the base
Danger
Touching live parts can result in serious
material damage or injuries, e.g. due to
fire or an electric shock.
Isolate before working on the device and
cover up live parts in the vicinity.
In case of non-observance, there is a risk of
personal liability for material damage and
injury!
1. Switch the mains voltage off.
2. Cut out the pre-perforated slots for cable
inlet using a suitable tool (e.g. knife).
3. Mount the base.
4. Connect the 230 V power supply on the
terminal block. Plan a conform circuit
breaker (accord. to EN 60950-1:2014-
08).
5. If desired, network more than one 230 V
base (up to 40 bases).
Note
Networking may only be "in series",
as signal transmission issues can result
otherwise.
Other types of networking (e.g. star-
shaped) are not permitted.
L
N
L
N
L
6. Switch on mains voltage.
7. Lock the smoke alarm device Dual Q
onto the base.
Operating and alarm signals
Signalling with the 230 V base
Signal tone
2
-
Loud inter-
3
val tone
loud pul-
sating sig-
nal tone
8 brief sig-
nal tones
(60 s cycle)
2 brief sig-
nal tones
(60 s cycle)
1 s-long
signal tone
in 2 s cycle
1 s-long
signal tone
in 2 s cycle
-
Brief sig-
nal tone in
1-s cycle
Brief
signal tone
in 250-ms
cycle
* Re-change the alarm device within 30 days.
Ring indicator
Please note the different signalling of the
ring indicator for "Fault" and "Weak
battery" when using the 230 V base and
powered by batteries only.
Signalling for wired or radio
networking
Signalling when a smoke alarm device is
triggered is as described above. The
networked smoke alarm devices signal as
follows:
Signal tone
Loud inter-
val tone
1 s-long sig-
nal tone in
2 s cycle
2 brief sig-
nal tones
N
(60 s cycle)
Ring
Meaning
indicator
-
Operating mode
Flashes
Local smoke
rapidly
alarm
Local heat
-
alarm
Fault/soiling
-
Weak battery*
-
Lights up
Function test
continuously
(alarm device
has triggered
alarm)
Flashes
Function test
rapidly
(alarm device
has not trig-
gered alarm)
-
Muting
EMC fault
-
Identification of
-
alarm device
Ring
Meaning
indicator
-
Smoke or heat
alarm message
Function test
-
(remote starting)
Weak battery*
-

Advertisement

loading

Summary of Contents for Gira Dual Series

  • Page 1 Device description Operating and alarm signals Installation and operating instructions Signalling with the 230 V base Ring Signal tone Meaning indicator 230 V base for Operating mode smoke alarm device Loud inter- Flashes Local smoke Dual val tone rapidly alarm 2331 02 loud pul- Local heat...
  • Page 2 Please submit or send faulty devices postage paid together with an error description to your responsible salesperson (specialist trade/installation company/ specialist electrical trade). They will forward the devices to the Gira Service Center. Gira Gira Giersiepen GmbH & Co KG Electrical installation systems P.O.

This manual is also suitable for:

Dual q2331 02