Friedrich Floating Air Pro-Premiere FPHW091 Service & Parts Manual page 15

Single zone
Hide thumbs Also See for Floating Air Pro-Premiere FPHW091:
Table of Contents

Advertisement

Capacities and Selection Data
Floating Air Pro / Premier Cooling Extended Capacity (By System Model)
System Model
FPHW091A
FPHW121A
FPHW093A
FPHW123A
15
SPECIFICATIONS
Outdoor Air
Temp. (°F DB)
‑5
5
14
17
23
32
35
47
59
‑5
5
14
17
23
32
35
47
59
‑5
5
14
17
23
32
35
47
59
‑5
5
14
17
23
32
35
47
59
Indoor Air Temp. °F DB / °F WB
TC
kBtu/h
‑7
3
12
15
19
28
33
43
50
‑7
3
12
15
19
28
33
43
50
‑7
3
12
15
19
28
33
43
50
‑7
3
12
15
19
28
33
43
50
80 /67
SHC
4.95
5.45
7.08
8.93
9.67
9.65
9.89
10.54
9.86
6.40
8.12
9.76
12.13
12.95
13.07
14.00
15.50
12.73
4.95
6.20
7.29
8.59
9.33
9.85
10.23
11.65
10.78
8.67
10.18
11.40
12.10
12.72
13.46
13.94
14.19
14.01
PI
kW
1.14
1.07
1.17
1.30
1.30
1.19
1.03
0.94
0.82
1.22
1.30
1.49
1.63
1.68
1.48
1.43
1.45
0.91
1.14
1.20
1.27
1.34
1.38
1.34
1.19
1.11
0.80
1.29
1.34
1.44
1.48
1.54
1.56
1.51
1.31
1.10

Hide quick links: