5
CHECK THERMOSTAT OPERATION
CONTINUED FROM FOURTH PAGE
9 Displays currently programmed set temperature (this is blank
when SYSTEM switch is in the OFF position).
10 "BATT" is displayed when 2 "AAA" batteries are low and
should be replaced.

Configuration Menu

The configuration menu allows you to set certain thermostat
operating characteristics to your system or personal requirements.
To enter the configuration menu, with SYSTEM switch in OFF
position, hold
and
configuration menu, move the SYSTEM switch from the OFF
position.
2. In the run mode, if the setpoint temperature is manually raised
by 3 F (2 C) or more above the actual temperature with the
TEMPERATURE UP key, and the fast second stage feature is
enabled, FA on, the second stage will energize immediately.
With FA off, second stage will not energize until the setpoint
temperature is 1 F or more above actual temperature for more
than ten minutes.
3. Select Compressor Lockout CL OFF or ON – Selecting CL
ON will cause the thermostat to wait 5 minutes before turning
on the compressor if the heating and cooling system loses
power. It will also wait 5 minutes minimum between cooling and
heating cycles. This is intended to help protect the compressor
from short cycling. Some newer compressors already have a
time delay built in and do not require this feature. Your com-
pressor manufacturer can tell you if the lockout feature is
already present in their system. When the thermostat compres-
sor time delay occurs it will flash the Snowflake and Flame
Icons for about five minutes.
4. Select Temperature Display Adjustment 3 LO to 3 HI –
Allows you to adjust the room temperature display up to 3 higher
or lower. Your thermostat was accurately calibrated at the
factory but you have the option to change the display temperature
to match your previous thermostat. The current or adjusted
room temperature will be displayed on the left side of the display.

TROUBLESHOOTING

7
Reset Operation
If a voltage spike or static discharge blanks out the display or
causes erratic thermostat operation you can reset the thermostat
by pressing
and
switched from "OFF" to "HEAT" position. This also resets the
factory defaults. If the thermostat has power, has been reset and
Symptom
No Heat/No Cool/No Fan
(common problems)
for at least two seconds. To exit the
at the same time when system is
Possible Cause
1. Blown fuse or tripped circuit breaker.
2. Furnace power switch to OFF.
3. Furnace blower compartment door or
panel loose or not properly installed.
Step
1
2
for at least 2 seconds
3
4
5*
6
* Not available on earlier models
5. Select Backlit Display – (Not available on earlier models) The
display backlight improves display contrast in low lighting
conditions. Selecting backlight ON will keep the light on
continuously. Selecting Backlight OFF will keep the light off.
6

SPECIFICATIONS

ELECTRICAL DATA
Electrical Rating:
20 to 30 VAC 50/60 Hz.
0.05 to 1.0 Amps (Load per terminal)
1.5 Amps Maximum Total Load (All terminals combined)
THERMAL DATA
Setpoint Temperature Range:
45 F to 90 F (7 C to 32 C)
Operating Ambient Temperature Range:
32 F to 105 F
Operating Humidity Range:
0 to 90% RH (non-condensing)
Shipping Temperature Range:
-40 F to 150 F
still does not function correctly contact your heating/cooling ser-
vice person or place of purchase.
Batteries
For optimum performance, we recommend replacing batteries
once a year with fresh "AAA" Energizer
www.white-rodgers.com
Configuration Menu
Press Button(s)
Displayed
(Factory Default)
Set SYSTEM
switch to OFF
and
FA
(ON)
and
CL
momentarily
(OFF)
and
0 HI
momentarily
(0)
dL
and
(ON)
momentarily
Move SYSTEM
Return to normal operation
switch from OFF
®
Corrective Action
Replace fuse or reset breaker.
Turn switch to ON.
Replace door panel in proper position to engage
safety interlock or door switch.
Press
or
to select:
OFF
ON
3 LO TO
3 HI
OFF
alkaline batteries.