8. COMPRESSOR CONTROL

1. OPEARTION FREQUENCY RANGE

The operation frequency of the compressor is different based on the operation mode as
shown in the table10.
(Table10 : Compressor Operation Frequency Range)
AOTG18KMTC
AOTG22KMTC
AOTG24KMTC

2. OPEARTION FREQUENCY CONTROL AT START UP

The compressor frequency soon after the start-up is controlled as shown in the Fig.9.
(Fig.9 : Compressor Control at Start-up)
Frequency
Frequency
Frequency
Frequency
Frequency
Frequency
(Frequency)
AOTG18/ 22/ 24KMTC
(Time)
AOTG18/ 22/ 24KMTC
Cooling
Min
Max
10rps
74rps
10rps
94rps
10rps
111rps
Time
Time
Time
Frequency
Frequency
Frequency
35rps
52rps
Time
Time
60sec
140sec
170sec
Heating
Min
Max
10rps
130rps
10rps
130rps
10rps
130rps
Time
Time
Frequency
Frequency
64rps
71rps
89rps
Time
Time
Time
200sec
350sec
01-09
Dry
Min
Max
18rps
24rps
18rps
24rps
18rps
24rps
Time
6
Frequency
97rps
Time
6
410sec