1.1 Digital electronic module 2RO NO DC24..120V/5A, AC24..230V/5A (6ES7132-4HB01-0AB0)
Switching capacity and lifetime of the contacts
With an external protective circuit, the contacts will last longer than specified in the table.
This table shows the switching capacity and endurance of the relay contacts:
Table 1-1
For resistive load
For inductive load in
accordance with IEC
947-5-1 DC 13/ AC 15
For inductive load in
accordance with IEC
947-5-1 DC 13/ AC 15
Digital electronic module 2RO NO DC24..120V/5A, AC24..230V/5A (6ES7132-4HB01-0AB0)
Manual, 04/2007, A5E01077282-01
Switching capacity and lifetime of the relay contacts
Resistive load
24 VDC
60 VDC
120 VDC
48 VAC
60 VAC
120 VAC
230 VAC
24 VDC
60 VDC
120 VDC
48 VAC
60 VAC
120 VAC
230 VAC
Voltage
5.0 A
4.0 A
2.0 A
1.0 A
0.5 A
0.1A
0.5 A
0.2 A
2.0 A
2.0 A
5.0 A
3.0 A
2.0 A
1.0 A
0.5 A
5.0 A
3.0 A
2.0 A
1.0 A
0.5 A
2.0 A
1.0 A
0.5 A
0.5 A
0.2 A
1.0 A
1.0 A
2.0 A
1.0 A
0.5 A
0.1A
2.0 A
1.0 A
0.5 A
Current
Operating cycles
0.1 million
0.2 million
0.5 million
1.6 million
4 million
7 million
1.6 million
1.6 million
1.6 million
1.2 million
0.1 million
0.2 million
0.4 million
0.8 million
1.5 million
0.1 million
0.2 million
0.4 million
0.8 million
1.5 million
0.1 million
0.2 million
0.5 million
0.2 million
0.5 million
0.7 million
0.5 million
0.1 million
0.3 million
1 million
2 million
0.1 million
0.3 million
1 million
Properties
(typical)
11