3.1.4. Drive Dimensions
D
E
+
A B C
STATUS 1
STATUS 2
1 2 3
4 5 6 7 8 9
10 11
EMC
L1 L2 L3
+
A
B
mm
in
mm
in
mm
226.3 8.9 215.2 8.5 201.4 7.9 165.3 6.5 144.8 5.7 182
Tightening Torques
Control Terminals
0.5 Nm
Power Terminals
1 Nm
3.1.5. Ventilation and Clearance
In order for the drive to maintain t's temperature, a minimum clearance is required around the drive as shown in the diagram below:
W
L1 L2 L3
X
W
X
mm
in
mm
20
0.787
78
The losses generated by each drive are explained in section 3. 1 .9. Cold-plate Capacity Calculation.
NOTE Value 'Z' is not applicable to the coldplate variant. These dimensions are the absolute minimum recommended clearances to
allow sufficient air flow. The enclosure itself must be significantly wider or taller than the values given above in at least one direction.