30
Wiring
Note: These are instructions for conduit wiring. For cable wiring, see the
Hardware
Note: In US deliveries, options are already installed at the factory. If installing on
site, see the appropriate option module manual for specific installation and wiring.
1. Install thin-wall conduit clamps for IP21/UL Type 1 or liquid-tight conduit connectors
for IP55/UL Type 12 (not supplied). Type 12 has a Pressfit gasket.
2. Connect conduit runs for input power, motor and control cables to the conduit box.
Ensure grommets (pointing down) are inserted into all unused holes.
3. Route the input power and motor wiring through separate conduits.
4. Strip wires.
5. Connect the motor and ground wires to the drive terminal. Tighten the screws to
torques shown in the Power wiring torque table.
Note: If you connect only one conductor to the connector, we recommend that you
put it under the upper pressure plate.
6. Connect the input power and ground wires to the drive terminal. Tighten the screws
to torques shown in the Power wiring torque table.
7. If parallel cables are used, install the parallel power cables.
8. Reinstall the shroud on the power terminals and the conduit box side plates.
9. Route the control cables through the conduit (not the same conduit as either input
power or motor wiring).
10. Strip the control cable sheathing and twist the copper shield into a pig-tail.
11. Refer to pages 31. Connect the ground shield pig-tail for digital and analog I/O
cables. (Ground only at drive end.)
12. Connect the ground shield pig-tail for Embedded fieldbus, EFB (EIA-485) cables at
X5. (Ground only at drive end.)
13. Strip and connect the individual control wires to the drive terminals. Tighten the
screws to torque table specifications on page 31.
ACH580 Ultra-Low Harmonic Drives Installation
ACH580 Ultra-Low Harmonic Drives Installation, Operation and Maintenance Manual
manual, publication number 3AXD50000044839.