Vibration Test; Cleaning; Safety Test - ebm-papst K3G250-PR17-I5 Operating Instructions Manual

Table of Contents

Advertisement

K3G250-PR17-I5
Impeller running
Imbalance in rotating
roughly
parts
Motor does not turn
Mechanical blockage
Mains supply voltage
faulty
Faulty connection
Overtemperature of
Insufficient cooling
electronics/motor
Thermal overload
protector responded
Ambient temperature
too high
Unacceptable
operating point
If you have any other problems, contact ebm-papst.

6.1 Vibration test

Checking the fan for mechanical vibrations based on ISO 14694.
Recommendation: every 6 months. Maximum vibration severity is 3.5
mm/s measured at the motor's fastening diameter on the motor support
plate towards and perpendicular to the motor's axis of rotation.
Item no. 54783-5-9970 · ENG · Revision 202174 · Release 2018-12-28 · Page 11 / 12
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
Operating instructions
Clean the device; if
imbalance is still
evident after cleaning,
replace the device.
If you have
attached any weight
clips during cleaning,
make sure to remove
them afterwards.
Switch off, de-
energise, and
remove mechanical
blockage.
Check mains supply
voltage,
restore power
supply,
apply control signal.
Fig. 4: Example showing vibration measurement. Positioning of the
De-energise, correct
sensors will vary depending on the device and the circumstances of
connection, see
installation.
connection diagram.

6.2 Cleaning

Improve cooling. Let
the device cool down.
To reset the error
message, switch off
the mains supply
voltage for a min. of
25 s and switch it on
again.
Allow motor to cool

6.3 Safety test

off, locate and rectify
cause of error, if
necessary cancel
restart lock-out
Reduce the ambient
temperature.
Reset by reducing
control input to 0.
Correct the operating
point. Let the device
cool down.
What has to
be tested?
Check the
protective
casing against
accidental
contact for
damage and to
ensure that it is
intact
Check the
device for
damage to
blades and
housing
Mounting the
connection lines
Check the
insulation of the
wires for damage
NOTE
Damage to the device during cleaning
Malfunction possible
→ Do not use a high-pressure cleaner to clean the device.# Do
not use any acid, alkali or solvent-based cleaning agents.
→ Do not use any pointed or sharp-edged objects for cleaning
NOTE
High-voltage test
The integrated EMC filter contains Y capacitors. Therefore, the
trigger current is exceeded when AC testing voltage is applied.
→ Test the device with DC voltage when you carry out the
high-voltage test required by law. The voltage to be used
corresponds to the peak value of the AC voltage required by
the standard.
How to test?
Frequency
Visual inspection At least every
6 months
Visual inspection At least every
6 months
Visual inspection At least every
6 months
Visual inspection At least every
6 months
Which
measure?
Repair or
replacement of
the device
Replacement of
the device
Fasten
Replace wires