Information Menu; Setup Menu - Worcester GB162 Series User Instructions

Wall hung gas fired condensing boiler
Hide thumbs Also See for GB162 Series:
Table of Contents

Advertisement

Status display


C
B
R
S
I
T
Table 3 Readings on the display
Menu O key
To change the settings, open the menu via the O key.
Down N and up M keys
You can navigate the various menus via the arrow keys. Press an arrow
key to change a setting or value.
Diagnostic plug
An external diagnostic tool can be connected here.
Burner LED
The Burner LED lights up when the burner is firing.
4.1

Information menu

After a few minutes of inactivity, the menu closes automatically and the
home screen is displayed.
Information on the status of the boiler can be read out via the information
menu. Proceed as follows:
▶ Press L to open the information menu.
▶ Navigate the menu with M and N keys in order to read out the
required data.
▶ Press L to exit the information menu.
Information menu
"info" is displayed for 1 second.
Maximum boiler flow temperature set [ °C]
during heating mode and chimney sweep
mode.
"OFF" appears in the display when heating
mode is switched off.
No information about DHW mode is shown
here.
Display of service code.
This information is only displayed if the boiler
requires a service intervention.
For a comprehensive overview of the display
codes and corresponding explanations see
Chapter 7.
Commercial Boiler Series – 6720814333 (2019/05)
Current flow temperature [°C]
Operating pressure [bar] (display
flashes if the operating pressure is
too low)
Chimney sweep mode (service
operation)
Burner in operation
Central heating
DHW
Pump running
Outside temperature display
An interlocking fault has occurred
or the boiler requires a service.
Information menu
Displays an operating code or fault code.
For a comprehensive overview of the display
codes and corresponding explanations see
Chapter 7.
Actual operating pressure [bar].
Current boiler flow temperature [ °C].
Outside temperature [ °C].
Only displayed with weather-compensated
control.
Calculated boiler flow temperature (setpoint)
[ °C] during heating mode R.
Current ionisation current [μA].
Current burner output [%] during heating
mode R. Mod = modulation
Current pump speed [%].
Mod = modulation
Table 4 Information menu
4.2

Setup menu

The boiler settings can be displayed and modified via the setup menu.
Proceed as follows:
▶ Press O to open the setup menu.
▶ Navigate the menu with M and N keys.
▶ Press and hold O to access a setting. Once the setting flashes it can
be modified.
▶ Change the setting via M and N keys.
▶ Press O to save the setting. The setting no longer flashes.
The display values shown are the default settings.
Setup menu
"menu" is displayed for 1 second.
Heating mode is switched on.
Setting: On, Off.
▶ Set the maximum boiler flow temperature
based on the heating system type.
Adjustment range: 30 - 90 °C.
Examples of settings:
• 40 °C
• 75 - 85 °C radiators
• 85 - 90 °C convectors
Operating the appliance
underfloor heating system
7