Note: If the power rating of the power supply unit is insufficient, the overcurrent protection characteristic can cause a voltage drop in all the outputs.
In order to trip the current according to the above characteristic, select a power supply unit with a current higher than the total tripping current
considering the power consumption of the S8V-CP.
Current and Voltage Tripping Characteristics
S8V-CP0424S
3.8
3.2
20
Note: 1. Input voltage 24 to 28.8 VDC tripping current is decreased to less than 3.2 A in accordance with the current and voltage tripping
characteristic.
2. Current tripping takes place between 250 ms to 5 s.