Omron S8V-CP Series Manual page 2

Dc electronic circuit protector (24 vdc 4 outputs/8 outputs type)
Hide thumbs Also See for S8V-CP Series:
Table of Contents

Advertisement

S8V-CP
Ratings, Characteristics, and Functions
Item
Rated input voltage
(Input voltage allowable range)
Allowable input current *1
Max. rated output current (per output)
Internal voltage drop *2
I/O
Output leakage current
characteristics
Power
consumption
(at input voltage
24 VDC) *3
Start-up time *4
Current tripping
function *6
Over voltage tripping function *6
Functions *5
Push button (ON/OFF/RESET)
with indicator
Reset signal input (RST)
Alarm signal output (ALM1/ALM2)
Dielectric strength
Insulation
Insulation resistance
Ambient operating temperature
Storage temperature
Environment
Ambient operating humidity
Vibration resistance
Shock resistance
MTBF *7
Reliability
Life expectancy *8
Weight
Construction
Cooling fan
Degree of protection
EMI
EMS
Standards
Safety standards
*1. For power input terminals, use 35 A max. per pole.
*2. A voltage drop will occur in the S8V-CP. Consider the voltage drop at the output.
*3. When selecting the power supply, be sure to include the power consumption of the S8V-CP and not just the power consumption of the load.
*4. Outputs start in order from +VO1 to +VO8. +VO1 starts after the initialization time. Start-up delay time of each output is automatically decided
depending on the load. If the start-up delay time is over 5 s, the next output is forcibly started.
*5. Refer to Tripping Functions on page 3 for details.
*6. Refer to Current Tripping Characteristics and Current and Voltage Tripping Characteristics on page 7 for details.
*7. MTBF is calculated according to JEITA RCR-9102.
*8. Refer to Recommended Replacement Periods and Periodic Replacement for Preventive Maintenance on page 14 for details.
*9. UL Class 2 output applies for the S8V-CP0424S model only.
2
Model
S8V-CP0424
Number of Outputs
UL Class 2 output
24 VDC
(20 to 30 VDC)
40 A
10 A
180 mV typ.
10 mA max.
When all outputs are
8 W typ. (at 10 A x 4 CH)
connected
When all outputs are
0.7 W typ.
tripped
Initialization time
250 ms typ.
Start-up delay time
50 ms to 5 s
2 A, 3 A, 4 A, 6 A,
Rated output current
8 A, 10 A
2.5 A, 3.5 A, 4.5 A, 6.5 A,
Cutoff current
8.5 A, 10.5 A
No
Yes (LED colors: Red/Green/Yellow)
Yes (High level: 20 to 30 VDC, Low level: 0 to 5 VDC)
Yes (MOS FET relay output 30 VDC max., 50 mA max.)
1.0 kVAC for 1 min (between all terminals and DIN rail mounting parts), current cutoff 20 mA
100 MΩ min. (between all terminals and DIN rail mounting parts) at 500 VDC
-25 to 70°C (Derating is required according to the temperature.) (with no condensation or icing)
-40 to 85°C (with no condensation or icing)
5% to 96% (storage humidity: 5% to 96%)
10 to 55 Hz, maximum 5 G, 0.42 mm half amplitude for 2 h each in X, Y, and Z directions
294 m/s
2
, 3 times each in ±X, ±Y, ±Z directions
135,000 hrs typ.
10 years min.
160 g max.
No
IP20 by IEC60529
Conforms to EN 61000-6-3
Conforms to EN 61000-6-2
UL 508 (CSA22.2 No.14-10) Listing Pol2
UL 2367 Recognition (Max. 100W per output, per Class 2 limitations) Pol2 *9
CE (EN 61000-6-2, EN 61000-6-3)
S8V-CP0424S
4
4
No
Yes
24 VDC
(20 to 28.8 VDC)
15.2 A
3.8 A
180 mV typ.
4 W typ. (at 3.8 A x 4 CH)
0.8 W typ.
3.8 A
3.8 A
Yes
60,000 hrs typ.
170 g max.
S8V-CP0824
8
No
24 VDC
(20 to 30 VDC)
70 A
10 A
200 mV typ.
15 W typ. (at 10 A x 7 CH)
1.1 W typ.
2 A, 3 A, 4 A, 6 A,
8 A, 10 A
2.5 A, 3.5 A, 4.5 A, 6.5 A,
8.5 A, 10.5 A
No
60,000 hrs typ.
420 g max.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

S8v-cp0424S8v-cp0424sS8v-cp0824

Table of Contents