FINAL INSTALLATION PROCEDURES

Location of DIP Switches on Multi F and Multi F MAX Outdoor Units

Figure 113: Multi F with LGRED (LMU180-240-300HHV) Outdoor Unit
DIP Switch Locations.
SW1

Forced Cooling Operation Function

Use to add refrigerant to the system when outside ambient temperatures are cool (ex.: winter).
1. Shut power down to the system.
2. Set DIP Switch 1 to ON.
3. Turn power on to the system.
4. Verify that the Red LED on the outdoor unit PCB is ON (indicates indoor units are in forced
cooling operation).
5. Add refrigerant.
• If the green LED light on the outdoor unit PCB is ON, it indicates the compressor is OFF due to
low pressure in the system.
• Turn DIP Switch 1 to OFF after finishing (Normal Operation setting).
• Only the first four DIP switches are functional on the LMU360, 420HHV.
84
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Figure 114: Multi F MAX with LGRED (LMU360-420HHV) Outdoor Unit
DIP Switch Locations.
F
MULTI
WITH
F
MULTI
MAX
Figure 115: LMU180-240-300HHV
Forced Cooling DIP Switch Setting.
3
ON
OFF
1 2
3
4
1 2
3
4
Figure 116: LMU360-420HHV Forced
Cooling DIP Switch Setting.
ON
OFF
1
2
3
4
5
6
7
8
5
5
5
9
10