Examples Of Supports; U-Bolt Support With An Insulated Pipe; O-Ring Band Support With An Insulated Pipe; Two-Point Down-Stop Support - LG MULTI F Series Installation Manual

Multi-zone heat pump systems with lgred 1.5 to 3.5 tons
Hide thumbs Also See for MULTI F Series:
Table of Contents

Advertisement

REFRIGERANT SYSTEM ENGINEERING

Examples of Supports

Figure 31: U-Bolt Support with Insulation.
Bolt
1.5t
Plate
Do not compress the insulation with the saddle-type support. If the insulation is compressed, it will tear open and allow condensation to
generate during product operation.
Figure 34: U-Bolt Support with an Insulated Pipe.
To prevent
insulation from
pressing and
lagging, use a cover.
Sheathing
Figure 36: One-Point Down-Stop Support (>441 lbs.).
Plate Nut
Hexagonal Nut
42
Figure 32: O-Ring Support with Insulation.
Insulation
PVC
Figure 35: O-Ring Band Support with an Insulated Pipe.
Figure 37: Two-Point Down-Stop Support.
O-ring Band
Welding
Insulated
Support Band
Down Stop
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Figure 33: Saddle-Type Support.
Bolt
PVC
O-Ring
Band
Lags
Sheathing
Welding
Insulated
Support Band
Refrigerant Pipe
F
MULTI
WITH
F
MULTI
MAX
Support at Intervals Between 5 and 6-3/4 Feet