General Mounting - Vertical / Horizontal Air Handler Units - LG MULTI V ARNU073M1A4 Installation Manual

Ducted indoor units
Table of Contents

Advertisement

Vertical / horizontal air handler units can be installed either in an upflow or a horizontal-left position.
General Guidelines
• Support platforms must be sturdy enough to support the air handler unit plus any accessories including filter boxes. The size of the
support must be bigger than the air handler unit; the unit itself must be placed at the center of the support.
• Vibration isolators (field-supplied) must be installed between the air handler unit and the support(s).
• Secure the plenum to support adapters and duct work.
• To prevent air leaks, seal all ducts following local codes.
• Follow all relevant building codes in installations in which an external condensate pan may be necessary. Supports for air handler units
must be located in or above the external condensate pan.
Specific Guidelines for Horizontal-Left Installation
• Units must not be installed where the access panels face up or down, nor where filter access is obstructed.
• If the air handler unit is suspended, use angled steel brackets with threaded rods as support.
• To ensure proper condensate drainage, the air handler unit must be installed so it is within 1/8" level of its length and
Figure 19: Upflow Installation.
Field-Supplied
Supply Duct
Field-Supplied
Return Plenum
GENERAL INSTALLATION GUIDELINES

General Mounting - Vertical / Horizontal Air Handler Units

Figure 20: Horizontal-Left Installation.
Field-Supplied
Supply Duct
More than 1-1/2
inch X 1-1/2 inch angle
Recommended
length more than 26
inch with 2 inch
clearance on both
sides of unit
Model No.
NJ Frames
ARNU123NJA4
ARNU183NJA4
ARNU243NJA4
ARNU303NJA4
ARNU363NJA4
NK Frames
ARNU423NKA4
ARNU483NKA4
ARNU543NKA4
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
More than 3/8 inch
threaded rod
C
Suspension Support Locations
Table 16: Horizontal-Left Installation Dimensions.
Capacity
(Btu/h)
A
12,000
18,000
24,000
4
30,000
36,000
42,000
48,000
4
54,000
width.
Field-Supplied
Return Plenum
A
B
Dimensions (inches)
B
23
41-3/8
29
48
C
37