Electrical − Low-Static Ducted L1/L2/L3 Chassis - LG MULTI V ARNU073M1A4 Installation Manual

Ducted indoor units
Table of Contents

Advertisement

GENERAL DATA
Electrical − Low-Static Ducted L1/L2/L3 Chassis
Table 11: Ducted Low Static L1, L2, L3 Chassis Indoor Unit Electrical Data.
Voltage
Model
Range
L1 Units
ARNU073L1G4
208-230
ARNU093L1G4
L2 Units
ARNU123L2G4
ARNU153L2G4
208-230
ARNU183L2G4
L3 Units
ARNU243L3G4
208-230
MCA : Minimum Circuit Ampacity.
MOP : Maximum Overcurrent Protection.
Units are suitable for use on an electrical system where voltage supplied to unit terminals is within the listed range limits.
Select wire size based on the larger MCA value.
Use a circuit breaker instead of fuses.
Max. power input is rated at maximum setting value.
1
22
Rated
MCA
MOP
Amps (A)
0.5
0.4
15
0.5
0.4
1.0
0.76
1.0
15
0.76
1.0
0.76
1.2
15
0.97
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Power Supply
Max.
Hz
Volts
Phase
Cooling
60
208-230
1
60
208-230
1
60
208-230
1
115
Power Input
(W)
1
Max.
L / M / H at Factory Default
Heating
40
40
24 / 28 / 31
40
40
24 / 29 / 39
85
85
29 / 34 / 41
85
85
34 / 41 / 56
85
85
41 / 56 / 71
115
48 / 63 / 103