Alarm and control system
Hide thumbs Also See for CANline 02:
Table of Contents

Advertisement

Quick Links

All rights are reserved by KIMESSA. Any reproduction, whether in hard or digital copy, even in part, without
written permission of KIMESSA-Swiss in any design and shape is prohibited.
The information in the documents are created according to current knowledge. Due to ongoing product deve-
KIMESSA AG
Rautistrasse 12
CH-8047 Zurich / Switzerland
Copyright © 2014 by KIMESSA –Switzerland
User Manual
CANline 02
Alarm and Control system
Copyright © 2015 by KIMESSA –Switzerland
lopments, technical changes or deviations may occur.
Page 1
Tel.:
+41 (0)44 404 38 38
Fax: +41 (0)44 404 38 39
Email info@kimessa.com
Home www.kimessa.com
CANline 02 Operating instructions 16.04.15hs/mb

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CANline 02 and is the answer not in the manual?

Questions and answers

Summary of Contents for Kimessa CANline 02

  • Page 1 Alarm and Control system Copyright © 2015 by KIMESSA –Switzerland All rights are reserved by KIMESSA. Any reproduction, whether in hard or digital copy, even in part, without written permission of KIMESSA-Swiss in any design and shape is prohibited. The information in the documents are created according to current knowledge. Due to ongoing product deve- lopments, technical changes or deviations may occur.
  • Page 2: Table Of Contents

    ARGET GROUP ELECTRICIANS AND MAINTENANCE TECHNICIANS PERSONAL PROTECTIVE EQUIPMENT USAGE .............................. 11 ...................................... 11 NTRODUCTION CANLINE 02 CONSTRUCTION ......................12 INSTALLATION ..........................13 ? ..........13 ONDITIONS OF USE NSTALLATION HERE AND HOW WILL THE CONTROL UNIT BE MOUNTED 02 ........................... 14...
  • Page 3 8.12 " " ................................ 36 XIT TO NORMAL OPERATION 8.13 "N " "E " ........................36 ORMAL OPERATION IN THE MAIN MENU DECLARATION OF CONFORMITY ....................37 Copyright © 2015 by KIMESSA –Switzerland Page 3/37 CANline 02 User Manual 18.11.15mb...
  • Page 4: General Information

    This applies both for property and for personal injury of any kind. KIMESSA disclaims any liability for any advice and execution errors by personnel which are not permanent employees of KIMESSA. Even if the dealer is acting on behalf of the company, they shall be liable for their own actions.
  • Page 5: Warranty

    1.4 Warranty KIMESSA AG guarantees the quality of all its products. It grants a guarantee on the material, under normal use and regular maintenance, for 12 months from the date of purchase. A later commissioning of the products does not extend the guarantee period, since for example sensors age due to storage conditions. KIMESSA shall re- pair or replace free of charge any part which proves to be defective within the warranty period.
  • Page 6: Risk / Potential Hazard

    1.8 Risk / Potential hazard KIMESSA gas detection systems and transmitters pose no risks subject to a proper and appropriate. use of our systems and components, these represent no hazard. A threat of non-execution or false alarm is only given when untrained and unauthorized personnel operate the gas detection system, transmitters and input signals.
  • Page 7 During installation and operation of the equipment, it must be ensured that no electrostatic charges (no high flow rate; cleaning with a damp cloth, etc.) occur on the plastic parts (type label, plastic housing). Copyright © 2015 by KIMESSA –Switzerland Page 7/37 CANline 02 User Manual 18.11.15mb...
  • Page 8: Definition Of The Signal Words

    Please note the regulations concerning the transport and storage of gas bottles. Gas detection systems are used for protection of persons and property and may be retrieved or serviced only by trained personnel. A product training and authorisation by KIMESSA is com- pulsory.
  • Page 9 If at the CANline 02 so-called ex-sensor is to be connected, it must meet the requirements for testing personnel (explosion protection) Tester Training Experience Timely action Instruction Usage; application regular use "Trained" Desired condition Annual training Person Possible faults Documented...
  • Page 10 PSA is not necessary Disposal Employee represen- the appropriate collection is per- None tatives formed according to EU Directive (2002/96 / EC) Copyright © 2015 by KIMESSA –Switzerland Page 10/37 CANline 02 User Manual 18.11.15mb...
  • Page 11: Usage

    3 alarm thresholds per measuring point and can be split into 2 fire/ventilation zones or groups. The CANline 02 control unit also has an alarm for over- and undershooting the measurement signal, with which relevant relays can be programmed that then, for example, visualize a fault accordingly.
  • Page 12: Canline 02 Construction

    3 CANline 02 Construction The CANline 02 consists of a lower part and an upper part, plastic, grey, RAL 7035. The lower part comes with mounting holes and carries the cable relief and cable glands for the connection cable between the sensor and the power supply.
  • Page 13: Installation

    The cable glands are mounted on the lower part of the CANline 02 housing, facing downwards. It is important to ensure that the gas detection control unit is always accessible. Note that the upper part of housing opens upwards for wiring, programming and during maintenance work.
  • Page 14: Mechanical Installation Of Can Line 02

    During installation and operation of the equipment, it must be ensured that no electrostatic charges (no high flow rate; cleaning with a damp cloth, etc.) occur on the plastic parts (type label, plastic housing). 4.2 Mechanical installation of CANline 02 When working on the gas detection system, use your personal protective equipment, safety boots, helmet, goggles, hand-held measuring instrument, respira- tory protection and, if necessary, hearing protection and gloves.
  • Page 15: Delivery Contents, Canline 02 Gas Detection Control Unit

    4.3 Delivery contents, CANline 02 gas detection control unit 4.4 CANline/opening/closing the control unit D = 212 mm L = 230 mm 4.5 Installation measurements E = 84 mm H = 90 mm W = 130 mm 26.5 mm W+ = 156.5 mm Open/close the gas detection control unit, remove it from/install it via the back panel by screwing in/unscrewing the housing screws (M3 flat screwdriver or M3 Phillips head screwdriver).
  • Page 16: Electrical Installation/Connecting The Control Unit

    In each case, the cable cross section must be calculated. The length of the + wire and the −wire and the total power consumption must be taken into consideration Copyright © 2015 by KIMESSA –Switzerland Page 16/37 CANline 02 User Manual 18.11.15mb...
  • Page 17: Kimessa-Cable

    The insulation and sheath are made of a special plastic (LSZH) which prevents halogen gases from being emitted in the case of a fire. KIMESSA electronics cables are therefore suitable for installation in public buildings (hospitals, theaters, etc. ). The good protection by the shield of a thin and effective copper braid allows for interference-free signal and impulse transfer.
  • Page 18: Electrical Installation/Emc And Atex

    Gland body and nut must be tightened with tight with the other hand. This way the braided a torque of 20 Nm shilded Rosette keeps its position. Copyright © 2015 by KIMESSA –Switzerland Page 18/37 CANline 02 User Manual 18.11.15mb...
  • Page 19 - ?-wired standard cable with shield - Conductor cross-section: 1 mm2 - Cable diameter 7.1 mm, KIMESSA special cable • Running cable - If risk of mechanical damage is possible, the cable must be appropriately protected (protective tube, etc.)
  • Page 20 - Check whether the device is ready for operation The parameterization for this application must be carried out All interfaces such as inputs and outputs for control purposes must be connected and ready. Copyright © 2015 by KIMESSA –Switzerland Page 20/37 CANline 02 User Manual 18.11.15mb...
  • Page 21: Canline 02 Connections

    Sensor 1 and 2 Bus-line (Analogue) connection 1 Connection Bus-line Connection Reset (exter- connection 2 Sensor 3 and 4 nal, digital) (Analogue) 230 VAC "inactive" power connec- Copyright © 2015 by KIMESSA –Switzerland Page 21/37 CANline 02 User Manual 18.11.15mb...
  • Page 22: Wiring Schematic For 2 X 4

    5.1 Wiring Schematic for 2 x 4..20mA detectors 5.2 Wiring Schematic for 2 x digital BUS detectors Copyright © 2015 by KIMESSA –Switzerland Page 22/37 CANline 02 User Manual 18.11.15mb...
  • Page 23 Copyright © 2015 by KIMESSA –Switzerland Page 23/37 CANline 02 User Manual 18.11.15mb...
  • Page 24: Wiring Schematic For Realy Contacst (Standard)

    5.3 Wiring Schematic for realy contacst (standard) Copyright © 2015 by KIMESSA –Switzerland Page 24/37 CANline 02 User Manual 18.11.15mb...
  • Page 25: User Comfort

    6 User comfort 6.1 Front view, dimensions and control elements Dimensions: Height 90 Width 230 Depth 130 Weight 1.10 kg 6.2 Front functions Copyright © 2015 by KIMESSA –Switzerland Page 25/37 CANline 02 User Manual 18.11.15mb...
  • Page 26: Alarm Reset

    With the appropriate programming of the CANline 02 control unit, in the event of an alarm, the acoustic alarm (signal horn) can be turned off by pressing the "RESET button" or by remote reset.
  • Page 27: Switching On

    7 Switching on After switching on the CANline 02, the firmware is loaded and various status mes- sages are displayed until the "boot up" sequence, which also serves to stabilize the sensors. Pellistor sensors, particularly, need to warm up. This can be Fig 4 TEST cancelled with the "RESET"...
  • Page 28: Main Menu

    - Sensor Settings - Sensor 1 and Sensor 2 - Relay 1 - Relay 5 are only in the visible variation, which allows for programming the CANline 02 control unit via the buttons. Copyright © 2015 by KIMESSA –Switzerland Page 28/37...
  • Page 29: Normal Operation / Sensor Display

    If you are in the Menu, the respective menu item is high- lighted in yellow, and the buttons Previous "<" ; "Ok" and forward ">" are visible in the display Copyright © 2015 by KIMESSA –Switzerland Page 29/37 CANline 02 User Manual 18.11.15mb...
  • Page 30: System Info Menu

    "Service Message Service Reset Now," whereby the display of the message returns to "System Info Next Service" in the menu without changing the setting of the interval. Copyright © 2015 by KIMESSA –Switzerland Page 30/37 CANline 02 User Manual 18.11.15mb...
  • Page 31: Quantity Of Sensors - System Info

    Return to "normal operation" by pressing the ">" button or "<" button until you reach "Exit": "OK" button; for "System Info," with ">" button or "<" button until you reach "Exit": "OK" button: for "Normal operation" Copyright © 2015 by KIMESSA –Switzerland Page 31/37 CANline 02 User Manual 18.11.15mb...
  • Page 32: Dc Voltage Info - System Power

    Return to "normal operation" by pressing the ">" button or "<" button until you reach "Exit": "OK" button; for "System Info," with ">" button or "<" button until you reach "Exit": "OK" button: for "Normal operation," Copyright © 2015 by KIMESSA –Switzerland Page 32/37 CANline 02 User Manual 18.11.15mb...
  • Page 33: Alarm History 1 ... 10 - S Ensor 3 Alarm - History 2 - System Info

    "Alarm History 1 ... 10" and then the ">" button or the "<" button to" Exit ": "OK" button; for "System Info," with ">" button or "<" button until you reach "Exit": "OK" button: for "Normal operation" Copyright © 2015 by KIMESSA –Switzerland Page 33/37...
  • Page 34: Relay Check 1 ... 5 / M Enu Structure / System Info

    Return to "normal operation" with the "OK" button; for "Relay check," "<" button or "<" button unto "Exit": "OK" button; for "Relay Check 1 ... 5,": "> Button" or "<button" until "Exit" "OK" button: for "Normal operati- on" Copyright © 2015 by KIMESSA –Switzerland Page 34/37 CANline 02 User Manual 18.11.15mb...
  • Page 35: Exit To Main Menu

    "Service Message" 8.11 Exit to main menu Likewise, by using the button functions ">", "OK / SELECT" and ">" buttons you can return to the main menu. Copyright © 2015 by KIMESSA –Switzerland Page 35/37 CANline 02 User Manual 18.11.15mb...
  • Page 36: Exit To "Normal Operation

    8.13 "Normal operation" via "Exit" in the main menu Likewise, by using the button functions ">", "OK / SELECT" and ">" buttons you can return to the main menu. Copyright © 2015 by KIMESSA –Switzerland Page 36/37 CANline 02 User Manual 18.11.15mb...
  • Page 37: Declaration Of Conformity

    Declaration of Conformity Copyright © 2015 by KIMESSA –Switzerland Page 37/37 CANline 02 User Manual 18.11.15mb...