TECHNICAL CHARACTERISTICS

ELECTRICAL CHARACTERISTICS

PARTNER LSA 49.1 alternator is a machine without
sliprings or revolving field brushes, wound as "2/3 pitch";
6 or 12-wire, with class H insulation and a field excitation
system available in either AREP or "SHUNT+PMG"
version (see diagrams and AVR maintenance manual).
Electrical options
- Stator temperature detection sensors
- Space heaters
- Terminal box with connector links for mounting
protection or measurement C.T.
In order to conform to standard EN 61000- 6.3, EN
61000-6.2, the R 791 interference suppression kit is
needed.
AREP system with R 450
EXCITER
Armature
Field
SHUNT + PMG system with R 450
EXCITER
Armature
Field
OPERATION & MAINTENANCE MANUAL
MAIN FIELD
MAIN FIELD
66

MECHANICAL CHARACTERISTICS

- Steel frame
- Cast iron end shields
- Greasable ball bearings
- Mounting arrangements:
IM 1201 (MD 35) foot and flange mounted, single-
bearing with SAE coupling disc.
IM 1001 (B 34) double-bearing with SAE flange and
standard cylindrical shaft extension.
- Drip-proof machine, self-cooled
- Degree of protection: IP 23
Mechanical options
- Protection against harsh environments
- Air inlet filter, air outlet labyrinth seals: IP 44
To prevent excessive temperature rise caused by
clogged filters, it is advisable to monitor the stator
winding with thermal sensors (PTC or PT100).
STATOR : 6 wires (marked T1 to T6)
STATOR : 12 wires (marked T1 to T 12)
Aux. windings
STATOR : 6 wires (marked T1 to T6)
STATOR : 12 wires (marked T1 to T 12)
Voltage reference
60 Hz: G655 - G750 - G800 - G850XW/XF
Voltage reference
50 Hz: G625 - G690 - G750XW/XF