Page 2
Input Channel (AI-1 thru AI-4, TI-1 or TI-2) Occupied Mode High Setpoint Occupied Mode Low Setpoint Due to continuous improvement, Triatek reserves the right to change product specifications without notice. Triatek reserves the right to change product specifications without notice.
Page 3
Delay Setting (0 – 60) Alarm Quiet Period Starting Hour (0 – 23) Alarm Quiet Period Ending Hour (0 – 23) Engineering Units Feet per Minute or Meters per Second Triatek reserves the right to change product specifications without notice.
Page 4
FAST ACTING ELECTRONIC ACTUATOR CORRECT CORRECT 120/24VAC, 30Va Transformer 120/24VAC, 20Va Third Party Supplied by Triatek Transformer Due to continuous improvement, Triatek reserves the right to change product specifications without notice. Triatek reserves the right to change product specifications without notice.
COMPREHENSIVE WIRING DIAGRAM ………………………………....…..………………………………………………………39 FLOW DIAGRAMS Unit Setup Tree…………………..........………..……………………………………………………………………40 System Setup Tree…………………………..…......…..……………………………………………………………………42 Display Setup Tree……………………………..........……………………………………………………………………45 Diagnostics Menu Tree…………….....……………......…………………………………………………………………………46 Due to continuous improvement, Triatek reserves the right to change product specifications without notice. Triatek reserves the right to change product specifications without notice.
Backlight Color…………………………………..…………………………………………………………………………..…………………………White Luminous Intensity……………………..…………………………………………………………………………………..………………min 2500 cd/m2 Due to continuous improvement, Triatek reserves the right to change product specifications without notice. Due to continuous improvement, Triatek reserves the right to change product specifications without notice. Triatek reserves the right to change product specifications without notice.
Page 7
- 1 - 1 HMS1655 Sensor Type Sash Sensor 1 = single smart sidewall sensor blank = sash sensor not included 2 = dual smart sidewall sensor S = sash position sensor included Triatek reserves the right to change product specifications without notice.
The HMS-1655’s Safety Halo™ is shipped from the temperature variances, the HMS-1655 provide two dedicated thermistor Due to continuous improvement, Triatek reserves the right to change product specifications without notice. Triatek reserves the right to change product specifications without notice.
Page 9
A unique feature of the HMS-1655 is its ability to trigger a relay output The HMS-1655 provides native support for multiple networking protocols, for the purpose of activating an optional automatic sash closer device,...
The control unit is typically secured in a convenient location on top of the fume hood. Due to continuous improvement, Triatek reserves the right to change product specifications without notice. Triatek reserves the right to change product specifications without notice.
MOUNTING/WIRING Case Dimensions 3" 3 / 4 " 1.13” Left Angle Side View ® Cable provided terminated at control unit Right Side View Control Unit 5" 3 / 4 " Triatek reserves the right to change product specifications without notice.
5.05” ø 0.143” The HMS-1655 display backplate may be mounted directly to a standard single-gang wall box using the two slots along the centerline. Use the backplate as a template to mark the mounting holes and the cable access hole at the center of the backplate.
If the hood is bypassed or in close proximity to items like baffles, deflectors, etc., contact the factory. 6.00" Due to continuous improvement, Triatek reserves the right to change product specifications without notice. Triatek reserves the right to change product specifications without notice.
Flexible Tubing (3 ft. Supplied) FIGURE 2 Alternate Sensor Mounting This port must be referenced to laboratory air for proper +Vin orientation and should be located away from turbulence. To HMS 1655 Triatek reserves the right to change product specifications without notice.
S1 - 1 = OFF, S1 - 5 = OFF (AI - 1 set as 0-5V Input) Due to continuous improvement, Triatek reserves the right to change product specifications without notice. Triatek reserves the right to change product specifications without notice.
HMS-1655 MOUNTING/WIRING Analog Output to Electric Actuator Controller Configuration Dipswitch Settings S1 - 1 = OFF, S1 - 5 = OFF (AI - 1 set as 0-5V Input) Triatek reserves the right to change product specifications without notice.
S1 - 1 = OFF, S1 - 5 = OFF (AI - 1 set as 0-5V Input) Due to continuous improvement, Triatek reserves the right to change product specifications without notice. Due to continuous improvement, Triatek reserves the right to change product specifications without notice.
S1 - 1 = OFF, S1 - 5 = OFF (AI - 1 set as 0 - 5V Input) S1 - 2 = OFF, S1 - 6 = OFF (AI - 2 set as 0 - 5V Input) Triatek reserves the right to change product specifications without notice.
S1 - 2 = OFF, S1 - 6 = ON (AI - 3 set as 0-10V Input) Due to continuous improvement, Triatek reserves the right to change product specifications without notice. Due to continuous improvement, Triatek reserves the right to change product specifications without notice.
Digital Input Occupancy Sensor Default input for occupancy sensor is DI-14, but also may be terminated at DI-2 or DI-3. Controller Configuration Slideswitch Settings S5 = Left (Active - Low Digital Input) Triatek reserves the right to change product specifications without notice.
HMS-1655 MOUNTING/WIRING Power Due to continuous improvement, Triatek reserves the right to change product specifications without notice. Triatek reserves the right to change product specifications without notice.
20A circuit breaker. This circuit breaker should be mounted in an approved electrical enclosure located separately, but in close proximity to this product. Triatek reserves the right to change product specifications without notice.
Controller Configuration Dipswitch Settings S3 - 7 = ON, S3 - 8 = ON (BACnet MS/TP protocol selected) Due to continuous improvement, Triatek reserves the right to change product specifications without notice. Triatek reserves the right to change product specifications without notice.
(REF) must be connected to the "NETWK REF" terminals at the backplane. Controller Configuration Dipswitch Settings S3 - 7 = ON, S3 - 8 = OFF (Metasys N2 Open protocol selected) Triatek reserves the right to change product specifications without notice.
• Configure analog output • Calibrate face velocity sensor Due to continuous improvement, Triatek reserves the right to change product specifications without notice. Triatek reserves the right to change product specifications without notice.
100) must be configured and calibrated accordingly. If this application will sound an audible alarm if the sash is left at or above this position Due to continuous improvement, Triatek reserves the right to change product specifications without notice. Triatek reserves the right to change product specifications without notice.
The sash low mute height specifies the height below which the on the next four screens to calibrate the sash position sensor for sash HMS-1655 will mute the audible alarm if it has been activated due to control operation.
Changing Network Settings by the HMS-1655, the analog output must be configured accordingly. Changing network settings on the HMS-1655 is simple and can be If this application requires monitoring only and does not include accessed by selecting Unit Setup >> Network Setup. Depending upon...
Options popup configuration screen. The air flow output from the UVM multi-level passwords to the system. A password entry may be created must be brought into analog input 4 (AI-4) at the HMS-1655, and this by selecting System Setup >> Next >> Passwords Setup >> Add input must be configured as a flow input using the System Setup menu.
ON = Enabled Mode Select OFF = FMS-1655 / CMS-1650 ON = HMS-1655 Operational Mode: OFF = Demo Mode ON = Run Mode Pushbutton Switch (SW1): Reset Button Pushbutton Switch (SW2): Reserved Triatek reserves the right to change product specifications without notice.
Page 32
ON = 0-10Vdc NOTES: To configure HMS-1655 for sidewall velocity sensor, set dipswitch positions 1 and 5 to OFF. To configure HMS-1655 for sash position sensor at AI-3 (default), set dipswitch position 3 to OFF and dipswitch position 7 to ON.”. For other inputs, see Table 1.
Page 33
LEFT = Analog Outputs powered by remote source LEFT = Digital Inputs pulled-high (triggered by active low input - default) RIGHT = Analog Outputs powered locally by HMS-1655 (default) RIGHT = Digital Inputs pulled-low (triggered by active high input, up to 24Vdc)
Page 34
AV - 26 AI-2 High Warning Setpoint Read/Write AV - 27 AI-2 High Alarm Setpoint Read/Write Due to continuous improvement, Triatek reserves the right to change product specifications without notice. Triatek reserves the right to change product specifications without notice.
Page 35
Duct Air Flow based on AI-4 flow input (Exhaust Flow) Read-Only AV - 53 Volumetric Offset (Supply Flow – Exhaust Flow) Read-Only AV - 54 Volumetric Offset Setpoint Read/Write AV - 55 AO-1 Override Level Read/Write Triatek reserves the right to change product specifications without notice.
Page 36
ADF - 3 Primary Alarm Relay Low Setpoint Read/Write ADF - 34 AI-4 High Warning Setpoint Read/Write Due to continuous improvement, Triatek reserves the right to change product specifications without notice. Triatek reserves the right to change product specifications without notice.
Hotspot Features of HMS-1655 Touchscreen Display Due to continuous improvement, Triatek reserves the right to change product specifications without notice. Triatek reserves the right to change product specifications without notice.
HMS-1655 FLOW DIAGRAMS Unit Setup Tree Due to continuous improvement, Triatek reserves the right to change product specifications without notice. Triatek reserves the right to change product specifications without notice.
Page 41
HMS-1655 FLOW DIAGRAMS Unit Setup Tree Triatek reserves the right to change product specifications without notice.
HMS-1655 FLOW DIAGRAMS System Setup Tree Due to continuous improvement, Triatek reserves the right to change product specifications without notice. Triatek reserves the right to change product specifications without notice.
Page 43
HMS-1655 FLOW DIAGRAMS System Setup Tree Triatek reserves the right to change product specifications without notice.
Page 44
HMS-1655 FLOW DIAGRAMS System Setup Tree Due to continuous improvement, Triatek reserves the right to change product specifications without notice. Triatek reserves the right to change product specifications without notice.
HMS-1655 FLOW DIAGRAMS Diagnostics Setup Tree Due to continuous improvement, Triatek reserves the right to change product specifications without notice. Triatek reserves the right to change product specifications without notice.
Page 47
HMS-1655 FLOW DIAGRAMS Notes Triatek reserves the right to change product specifications without notice.
Page 48
Triatek’s customer service is unparalleled. Our product support system includes on-site installations, phone support, repairs, calibrations, and in-depth training sessions. From our knowledgable engineers and sales team to our talented field technicians, Triatek goes above and beyond to ensure our products are installed correctly and our customers’ critical environments are working properly.
Need help?
Do you have a question about the HMS-1655 and is the answer not in the manual?
Questions and answers