Page 2
FMS-1655 Notes Triatek reserves the right to change product specifications without notice.
Page 3
Failure to follow the wiring diagrams could result in damage to your equipment and could void your warranty. Wiring diagrams can also be found at www.triatek.com. Under no circumstances should a single transformer be split between actuator and controller. Doing so will damage the actuator, the transformer, the controller or all units.
Page 4
This form should be completed during the initial configuration for each room pressure controller. Be sure to configure the unit for either Positive, Negative, or both using the Isolation Mode Configuration setup procedure. See FMS-1655 Wiring and Installation Manual for details.
Page 5
Delay Time Base (secs or mins) Delay Setting (0 – 60) Alarm Quiet Period Starting Hour (0 – 23) Alarm Quiet Period Ending Hour (0 – 23) Engineering Units Inches of Water or Pascals Triatek reserves the right to change product specifications without notice.
Configuring Room Pressure Monitor ………………………………………………………………………………………………… 41 Setting Up Analog Output ……………………………………………………………………………………………………………… 41 Enabling Door Switch ……………………………………………………………………………………………………………… 41 - 42 Due to continuous improvement, Triatek reserves the right to change product specifications without notice. Triatek reserves the right to change product specifications without notice.
Page 7
Unit Setup Tree…………………………………..……………………………………………………………………………………… 59 System Setup Tree……………...…………………………………………………………………………………………………… 60 - 62 Display Setup Tree…………..…………………………………………………………………………………………………………… 63 Diagnostics Tree………………..………………………………………………………………………………………………………… 64 Due to continuous improvement, Triatek reserves the right to change product specifications without notice. Triatek reserves the right to change product specifications without notice.
Recommended Cable Type (applicable to surface mount models FMS-1655-s-x only)…………………………………………………… Belden 3125A Mechanical FMS-1655 Internal Sensor Flush Mount Housing (Brushed Stainless Steel) Housing..……………………………………………5.6”W x 8.5”H x 1.9”D FMS-1655 Display Module Housing………………………………………………………………………………………………………3”W x 5”H x 1.13”D Stainless Steel Cover Plate for Flow Tube……………………………………………………………………………………………2.7”W x 4.5”H x 0.2”D Stainless Steel Cover Plate for Remote Sensor………………………………………………………………………………………2.7”W x 4.5”H x 0.2”D...
This Class-A digital apparatus complies with Canadian ICES-003. Cet appareil numérique de la classe-A est conforme à la norme NMB-003 du Canada. Triatek reserves the right to change product specifications without notice.
Metasys® N2) for easy integration with either directly from the touchscreen display or (NTC) Type 2 or Type 3 sensors. Due to continuous improvement, Triatek reserves the right to change product specifications without notice. Triatek reserves the right to change product specifications without notice.
Page 11
FMS-1655 GENERAL Overview The FMS-1655 provides four universal A unique feature of the FMS-1655 is its ability FMS-1655L series) The configuration of the analog outputs, which may be configured for to trigger a relay output based on the current desired protocol is field selectable through the...
Cut the tubing as needed to leave power up delay, the unit will display a brief five backplate. approximately two inches protruding. Press Triatek reserves the right to change product specifications without notice.
Page 13
Safety Halo™ status matches that of the main display screen. FMS-1655 units are shipped from the factory in neutral isolation mode. Triatek reserves the right to change product specifications without notice.
Page 14
Internal Sensor The FMS-1655 is calibrated with settings programmed in the factory according to the customer specifications. The user can change the settings by using the instructions provided in the Quick Start section of this manual beginning on page 38.
FMS-1655 MOUNTING/WIRING Notes Triatek reserves the right to change product specifications without notice. Triatek reserves the right to change product specifications without notice.
AI_1 3.65” H x 2.15” W. If more than one remote sensor is being 2. Drill a 7/16” hole through the opposite wall used with the FMS-1655, then each must Triatek reserves the right to change product specifications without notice.
To FMS-1655 Controller clamps for secure wall attachment. Standard Remote Sensor Detail (Side View) Triatek reserves the right to change product specifications without notice.
Page 18
Wall Section Gasket penetration) (cutaway view) CORRIDOR Stainless Steel Mounting Plate Standard Remote Sensor Detail (Bottom View) Triatek reserves the right to change product specifications without notice.
Remote Sensor Configuration The electrical connections to the FMS-1655 made via a convenient backplate/backplate assembly is shown below. All wiring should conform to the local regulations and National Electric Code. Take care not to run sensor wiring in the same conduit as the line voltage or other conductors that supply highly inductive loads such as generators, motors, solenoids, contactors, etc.
S1 - 2 = ON, S1 - 6 = OFF (AI - 2 set as 4 - 20mA Input) S4 - 1 = ON (AO - 1 set as Voltage Output) Triatek reserves the right to change product specifications without notice.
Page 21
S1 - 2 = ON, S1 - 6 = OFF (AI - 2 set as 4 - 20mA Input) S4 - 1 = ON (AO - 1 set as Voltage Output) Triatek reserves the right to change product specifications without notice.
S1 - 2 = ON, S1 - 6 = OFF (AI - 2 set as 4 - 20mA Input) S4 - 1 = ON (AO - 1 set as Voltage Output) Triatek reserves the right to change product specifications without notice.
S1 - 2 = ON, S1 - 6 = OFF (AI - 2 set as 4 - 20mA Input) S1 - 4 = ON, S1 - 8 = OFF (AI - 4 set as 4 - 20mA Input Triatek reserves the right to change product specifications without notice.
Controller Configuration Dipswitch Settings S1 - 1 = ON, S1 - 5 = OFF (AI - 1 set as 20mA Input) S4 - 1 = ON (AO - 1 set as Voltage Output) Triatek reserves the right to change product specifications without notice.
Controller Configuration Dipswitch Settings S1 - 1 = ON, S1 - 5 = OFF (AI - 1 set as 20mA Input) S4 - 1 = ON (AO - 1 set as Voltage Output) Triatek reserves the right to change product specifications without notice.
Step Down Isolation Transformer (provided with FMS Controller) Controller Configuration Dipswitch Settings S1 - 2 = ON, S1 - 6 = OFF (AI - 2 set as 4 - 20mA Input) Triatek reserves the right to change product specifications without notice.
S1 - 1 = ON, S1 - 5 = OFF (AI - 1 set as 4 - 20mA Input) S1 - 2 = ON, S1 - 6 = OFF (AI - 2 set as 4 - 20mA Input) Triatek reserves the right to change product specifications without notice.
S1 - 2 = ON, S1 - 6 = OFF (AI - 2 set as 4 - 20mA Input) S1 - 3 = ON, S1 - 7 = OFF (AI - 3 set as 4 - 20 mA Input) Triatek reserves the right to change product specifications without notice.
S1 - 3 = ON, S1 - 7 = OFF (AI - 3 set as 4 - 20 mA Input) S1 - 4 = ON, S1 - 8 = OFF (AI - 4 set as 4 - 20 mA Input) Triatek reserves the right to change product specifications without notice.
Isolation Transformer (provided with FMS Controller) The above example associates the Thermistor with contacts T1 and AGND for illustrative purposes only. In fact, either of the two T#s can be used. Triatek reserves the right to change product specifications without notice.
Page 32
Step Down Isolation Transformer (provided with FMS Controller) Controller Configuration Dipswitch Settings S1 - 2 = OFF, S1 - 6 = ON (AI - 2 set as 0 - 10V Input) Triatek reserves the right to change product specifications without notice.
Digital Input to Door Switch A switch having normally-open or normally close contacts may be used with the FMS-1655 to serve as a timed alarm buzzer inhibit, when the room door has been opened. An optional door switch (part number SWD-100) may be purchased from Triatek for this specific purpose.
DI4 and DGND for illustrative purposes only. In fact, any of the four DI#s can be used. Controller Configuration Slideswitch Settings S5 = Left (Active - Low Digital Input) Triatek reserves the right to change product specifications without notice.
The above example associates Monitor Output 1 with contacts RL3 and RL3_C for illustrative purposes only. In fact, any of the four RL#s (and the corresponding RL#_C) can be used. Triatek reserves the right to change product specifications without notice.
The above example associates Monitor Output 2 with contacts RL4 and RL4_C for illustrative purposes only. In fact, any of the four RL#s (and the corresponding RL#_C) can be used. Triatek reserves the right to change product specifications without notice.
The above example associates Heating State 1 with contacts RL1 and RL1_C for illustrative purposes only. In fact, any of the four RL#s (and the corresponding RL#_C) can be used. Triatek reserves the right to change product specifications without notice.
The above example associates Heating State 2 with contacts RL2 and RL2_C for illustrative purposes only. In fact, any of the four RL#s (and the corresponding RL#_C) can be used. Triatek reserves the right to change product specifications without notice.
FMS-1655 SUBHEAD MOUNTING/WIRING Power Step Down Isolation Transformer (provided with FMS Controller) Triatek reserves the right to change product specifications without notice.
This product should be installed with the manufacturer provided isolated power supply and connected to an electrical circuit protected by a minimum 20A circuit breaker. This circuit breaker should be mounted in an approved electrical enclosure located separately, but in close proximity to this product. Triatek reserves the right to change product specifications without notice.
Page 42
FMS-1655 MOUNTING/WIRING SUBHEAD Notes Triatek reserves the right to change product specifications without notice.
(REF) must be connected to the "BMS NETWK REF" terminals at the backplane. Controller Configuration Dipswitch Settings S3 - 7 = ON, S3 - 8 = ON (BACnet MS/TP protocol selected) Triatek reserves the right to change product specifications without notice.
(REF) must be connected to the "NETWK REF" terminals at the backplane. Controller Configuration Dipswitch Settings S3 - 7 = ON, S3 - 8 = OFF (Metasys N2 Open protocol selected) Triatek reserves the right to change product specifications without notice.
The information that is displayed on the main at this screen as well providing an audible screen includes the following from top to alert of the unsafe conditions. bottom: The FMS-1655 incorporates a full-color Triatek reserves the right to change product specifications without notice.
If the door Configure door switch range of the actual analog output signal. switch option is enabled, the main display will Triatek reserves the right to change product specifications without notice.
The Safety Halo™ feature is exclusive to the which is considered normal, as well as the Cycle is completed, a message will appear 1655 series of controllers from Triatek, and Triatek reserves the right to change product specifications without notice.
1655 for volumetric offset control, simply and remain in effect through a power cycle. A unique feature of the FMS-1655 is the Real- configure AI-3 as the supply flow input, The Display Modes menu option on the Time View option, which allows the user to and AI-4 as the exhaust flow input.
Page 49
FMS-1655 QUICK START GUIDE Notes Triatek reserves the right to change product specifications without notice.
ON = Enabled Mode Select OFF = FMS-1655 / CMS-1655 ON = HMS-1655 Operational Mode: OFF = Demo Mode ON = Run Mode Pushbutton Switch (SW1): Reset Button Pushbutton Switch (SW2): Reserved Triatek reserves the right to change product specifications without notice.
NOTES: To configure FMS-1655 for an internal sensor, set dipswitch position 1 to OFF and dipswitch position 5 to OFF. To configure FMS-1655 for a remote sensor, set dipswitch position 1 to ON and dipswitch position 5 to OFF. For other inputs, see Table 1.
ON = 0 - 5 Vdc Controller Configuration Slideswitch (S5): LEFT = Digital Inputs pulled-high (triggered by active low input - default) RIGHT = Digital Inputs pulled-low (triggered by active high input, up to 24Vdc) Triatek reserves the right to change product specifications without notice.
AV - 17 Alarm Relay 4 High Setpoint Read/Write AV - 18 Alarm Relay 4 Low Setpoint Read/Write AV - 19 AI-1 Low Alarm Setpoint (low differential pressure alarm) Read/Write Triatek reserves the right to change product specifications without notice.
Hot-Spot Features of FMS-1655 Touch Screen Display Due to continuous improvement, Triatek reserves the right to change product specifications without notice. Triatek reserves the right to change product specifications without notice.
FMS-1655 FLOW DIAGRAMS Display Setup Menu Tree Due to continuous improvement, Triatek reserves the right to change product specifications without notice. Triatek reserves the right to change product specifications without notice.
FMS-1655 FLOW DIAGRAMS Diagnostics Menu Tree Triatek reserves the right to change product specifications without notice.
Page 70
Laboratories Classrooms Vivariums Hospitals Triatek 1650 Triatek • 4366 Shackleford Road • Suite B • Norcross, GA 30342 • 888-242-1922 or 770-242-1922 • www.triatek.com The Next Generation in Critical Airflow Controls...