General Mounting
Securely attach the outdoor unit to a condenser pad,
base rails, or other mounting platform that is secure-
ly anchored to the ground or building structure. See
the figures below, and follow the applicable local
codes for clearance, mounting, anchor, and vibration
attenuation requirements.
• Location must be strong enough to bear the weight
and vibration of the outdoor unit.
• The outdoor unit supports must have a minimum
height of 7-7/8 inches, and a minimum width of
• Anchor bolts must be installed at least three (3) inches into the support.
• I-Beams can be used as a base support.
• Operation sound and vibration from the outdoor units
may transfer to surrounding floors or walls; to reduce
vibration and operation sound, add anti-vibration
materials to the concrete base.
• Ensure there is enough room under the outdoor unit
if installing the piping and wiring using the bottom
access holes.
WARNING
• The corners of the outdoor unit must be attached firmly to the
support, otherwise, the bolts may bend, cause the outdoor unit
to fall, which may result in physical injury or death.
• Attach the bolts tightly as shown to ensure the outdoor unit
will not fall due to earthquakes or strong wind gusts, causing
physical injury or death.
GENERAL INSTALLATION GUIDELINES
Figure 11:
Figure 12:
Figure 14:
Anti-Vibration
Materials
Concrete
Base
3"
Anchor Bolt
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.

Mounting the Outdoor Unit

Center of the Unit
At least 7-7/8 Inches
I-Beam Support
Figure 13:
36-1/4
24-5/16
5-15/16
Figure 15:
Minimum
Three (3)
Thread Ridges
I-Beam
7-7/8"
3-15/16"
Outdoor Units Should
r Unit
Not be Supported Only
pported Only
Center of the Unit
By the Corners
Anti-Vibration
Materials Between
the Outdoor Unit and
Support
Space for Bottom Install
Wiring and Piping
Concrete Support
5-15/16
13 14-1/4
Spring Washer
Frame
Nut
Anti-Vibration
Materials
Concrete
Base
3"
7-7/8"
Anchor Bolt