Type ACE95JR
BLANKETING GAS
SUPPLY LINE
E0620
of the national Fire Codes of the national
Fire Protection Agency or by other
applicable codes) to prevent service
conditions from exceeding those limits.
Additionally, physical damage to the
tank blanketing system could result in
personal injury and property damage due
to escaping accumulated gas. To avoid
such injury and damage, install the tank
blanketing valve in a safe location.
This Type ACE95jr tank blanketing valve was
assembled and preset to the customer specified
pressure and setpoint. The control pressure range of
the valve is stamped on the nameplate fastened to the
upper actuator case. The gas blanketing setpoint is the
only adjustable feature on this unit.
1. Get a qualified personnel when installing, operating,
and maintaining valves. Before installing, inspect
the valve and tubing for any shipment damage or
foreign material that may have collected. Make
4
SHUTOFF
VALVE
LINE STRAINER
TANK VENT
TANK
Figure 3. Type ACE95jr Tank Blanketing Valve Installation
TYPE ACE95jr
TYPE 252
INLET
FILTER
SHUTOFF
VALVE
BLANKETING GAS
TO TANK
BLANKETING GAS/VAPOR SPACE
LIQUID
certain the body interior is clean and the pipelines
are free of foreign material. Apply pipe compound
only to the male pipe threads with a screwed
body or use suitable line gaskets and good bolting
practices with a flanged body.
2. Inspect the nameplate on the upper actuator
case. It displays the model number, serial number,
a blanketing gas supply pressure range, the
maximum inlet pressure, set pressure and C
value. These must agree with the system that you
are blanketing. The serial number will be needed in
any communication with your local Sales Office.
3. Clean the gas blanketing supply lines of all dirt
and foreign material before connecting them to the
Type ACE95jr tank blanketing valve.
4. The valve must be mounted so the actuator case is
horizontal, as shown in Figure 3. The valve should
be mounted above the tank. Three connections are
required: a) blanketing gas supply to valve, b) valve
outlet to tank and c) sensing line to tank.
SENSING
LINE
SHUTOFF
VALVE
EMERGENCY
TANK VENT
v