Preparation Of Piping - LG MULTI V VJ Series Installation Manual

Indoor unit, ceiling suspended convertable
Hide thumbs Also See for MULTI V VJ Series:
Table of Contents

Advertisement

Installation

Preparation of Piping

Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following procedure.
1. Cut the pipes and the cable.
Use the accessory piping kit or the pipes purchased
locally.
Measure the distance between the indoor and the out-
door unit.
Cut the pipes a little longer than measured distance.
Cut the cable 1.5m longer than the pipe length.
2. Burrs removal
Completely remove all burrs from the cut cross section
of pipe/tube.
Put the end of the copper tube/pipe to downward direc-
tion as you remove burrs in order to avoid to let burrs
drop in the tubing.
3. Flaring work
Carry out flaring work using flaring tool as shown below.
Indoor unit
[kW(Btu/h]
Gas
<5.6(19,100)
1/2"
<16.0(54,600)
5/8"
<22.4(76,400)
3/4"
Firmly hold copper tube in a bar(or die) as indicated
dimension in the table above.
4. Check
Compare the flared work with figure below.
If flare is noted to be defective, cut off the flared section
and do flaring work again.
FLARE SHAPE and FLARE NUT TIGHTENING TORQUE
Precautions when connecting pipes
• See the following table for flare part machining dimensions.
• When connecting the flare nuts, apply refrigerant oil to the inside and outside of the flares and turn them three
or four times at first. (Use ester oil or ether oil.)
• See the following table for tightening torque.(Applying too much torque may cause the flares to crack.)
• After all the piping has been connected, use nitrogen to perform a gas leak check.
pipe size
Ø6.35
Ø9.5
Ø12.7
Ø15.9
10
Indoor Unit
Pipe
" A "
Liquid
Gas
Liquid
1/4"
0.5~0.8
0~0.5
3/8"
0.8~1.0 0.5~0.8
3/8"
1.0~1.3 0.5~0.8
tightening torque(Ncm)
1400~1600
3270-3990
4950-6030
6180-7540
Copper
tube
Point down
Bar
"A"
Copper pipe
Clamp handle
Smooth all round
Inside is shining without scratches.
Even length
all round
A(mm)
8.7~9.1
12.8-13.2
16.2-16.6
19.3-19.7
Slanted Uneven Rough
90°
Pipe
Reamer
Handle
Bar
Yoke
Red arrow mark
= Improper flaring =
Inclined
Surface
Cracked Uneven
damaged
flare shape
±2
90°
A
R=0.4~0.8
Cone
thickness