PROTOCOL
BACnet MS/TP (Master)
Modbus (Slave)
N2 (Slave)
LonWorks
NOTE:
DS = Dip Switch
BACnet MS/TP SW3 example shown
Baud Rate Selections
BAUD RATE
9600
19,200
38,400
76,800
MSB
SW1
Fig. 118 — RTU Open Controller Address Switches
J19
Fig. 119 — Network Wiring
SW3 Protocol Selection
DS8
DS7
Unused
OFF
Unused
OFF
Unused
OFF
Unused
ON
DS2
DS1
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Fig. 117 — RTU Open Controller SW3 Dip Switch Settings
LSB
SW2
DS6
DS5
DS4
OFF
OFF
ON
OFF
ON
ON
OFF
OFF
ON
ON
OFF
ON
UNUSED
(OFF)
(ON)
PROTOCOL SELECTOR DIP SWITCHES

Local Access

WALL MOUNTED EQUIPMENT TOUCH INTER-
FACE — The Equipment Touch interface is a wall mounted
interface used to connect to the RTU Open controller to access
the control information, read sensor values, and maintenance.
This is an accessory interface that does not come with the RTU
Open controller. You wire the Equipment Touch interface to
the RTU Open controller's J13 local access port. There are 2
password protected levels in the display (User and Admin). See
the Equipment Touch Installation and Setup Guide for more in-
formation. See Appendix A for navigation and screen content.
FIELD ASSISTANT — Field Assistant is a computer pro-
gram included with the purchase of the Tech Tool Kit (USB-
TKIT). This is a field Tech Tool to set-up, service, or download
application software to the RTU Open controller and includes a
USB Link Cable. The link cable connects a USB port to the
J12 local access port. The Field Assistant's menu structure is
similar and functions the same as i-Vu
120.
RTU OPEN CONTROLLER TROUBLESHOOTING
Communication LEDs
is speaking to the devices on the network. The LEDs should re-
flect communication traffic based on the baud rate set. The
higher the baud rate the more solid the LEDs will appear. See
Table 26.
NOTE: Refer to the RTU Open Multi-Protocol Controller
Controls, Start-Up, Operation and Troubleshooting manual for
complete configuration of the RTU Open controller, operating
sequences and troubleshooting information. Refer to the RTU
Open v3 Integration Guide for details on configuration and
troubleshooting of connected networks. Have a copy of these
manuals available at unit start-up.
72
DS3
DS2
Select
OFF
Baud
Select
OFF
Baud
ON
OFF
OFF
OFF
COMM
OPTION
SET TO
PORT
SET TO MSTP
38.4k
(MASTER)
BAUD
controller. See Fig.
®
The LEDs indicate if the controller
DS1
Select Baud
Select Baud
OFF
ON