50TC 16 UNIT SIZE

WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Unit cabinet must have an uninterrupted, unbroken electri-
cal ground to minimize the possibility of personal injury if
an electrical fault should occur. This ground may consist of
electrical wire connected to unit ground lug in control com-
partment, or conduit approved for electrical ground when
installed in accordance with NEC (National Electrical
Code); ANSI/NFPA 70, latest edition (in Canada, Cana-
dian Electrical Code CSA [Canadian Standards Associa-
tion] C22.1), and local electrical codes.
NOTE: Check all factory and field electrical connections for
tightness. Field-supplied wiring shall conform with the limita-
tions of minimum 63°F (33°C) rise.
Field Power Supply — For those units without through-the-
curb power, conduit must be used to route the main power from
the condenser end, via the power entry in the corner post of the
unit (see Fig. 37-39) to either the factory option disconnect or
the bottom of the control box. 1-in. conduit is provided
wrapped around compressor. A second conduit is provided
with factory installed powered convenience outlet. For those
units that require conduit larger than 1-in., it must be field sup-
plied. Figures 37-39 show the wire routings.
If the field disconnect is larger than 100A, it must be at-
tached to the unit using accessory CRDISBKT001A00 — dis-
connect switch bracket (see Fig. 40). Follow the instructions
provided with this accessory. For smaller field disconnects, be
sure to use
1
/
-in. screws to mount the disconnect directly to the
2
end panel (see Fig. 41). In either case, set the disconnect verti-
cal location on the unit so that a 90 degree fitting can be used to
connect the conduit to the disconnect.
Fig. 37 — Conduit into Factory Option Disconnect
Fig. 38 — Conduit into Control Box
Fig. 39 — Conduit into Single Point Box
Fig. 40 — Mounting Position for Field Disconnects
24
(over 100A)