Installation; Jobsite Survey; Step 1 - Plan For Unit Location - United Technologies Carrier WeatherMaker 50TC A08 Series Installation Instructions Manual

Single package rooftop cooling only with puron (r-410a) refrigerant
Table of Contents

Advertisement

LOCATION
DIMENSION
48-in. (1219 mm)
18-in. (457 mm)
A
18-in. (457) mm
12-in. (305 mm)
42-in. (1067 mm)
B
36-in. (914 mm)
Special
36-in. (914 mm)
C
18-in. (457 mm)
48 in. (1219 mm)
42-in. (1067 mm)
D
36-in. (914 mm)
Special
NOTE: Unit not designed to have overhead obstruction. Contact Application Engineering for guidance on any application planning overhead
obstruction or for vertical clearances.

INSTALLATION

Complete the following checks before
Jobsite Survey —
installation.
1. Consult local building codes and the NEC (National
Electrical Code) ANSI/NFPA 70 for special installation
requirements.
2. Determine unit location (from project plans) or select unit
location.
3. Check for possible overhead obstructions which may in-
terfere with unit lifting or rigging.
Step 1 — Plan for Unit Location —
tion for the unit and its support system (curb or other) that pro-
vides for the minimum clearances required for safety. This in-
cludes the clearance to combustible surfaces, unit performance
and service access below, around and above unit as specified in
unit drawings. See Fig. 7.
C
B
Unit disconnect is mounted on panel
No disconnect, convenience outlet option
Recommended service clearance
Minimum clearance
Surface behind servicer is grounded (e.g., metal, masonry wall)
Surface behind servicer is electrically non-conductive (e.g., wood, fiberglass)
Check sources of flue products within 10-ft of unit fresh air intake hood
Side condensate drain is used
Minimum clearance
No flue discharge accessory installed, surface is combustible material
Surface behind servicer is grounded (e.g., metal, masonry wall, another unit)
Surface behind servicer is electrically non-conductive (e.g., wood, fiberglass)
Check for adjustable units or building fresh air intakes within 10 ft (3 m) of this units flue outlet
Fig. 5 — Service Clearance Dimensional Drawing
Select a loca-
A
CONDITION
NOTE: Consider also the effect of adjacent units.
Unit may be installed directly on wood flooring or on Class
A, B, or C roof-covering material when roof curb is used. Do
not install unit in an indoor location. Do not locate air inlets
near exhaust vents or other sources of contaminated air.
Although unit is weatherproof, avoid locations that permit
water from higher level runoff and overhangs to fall onto the
unit.
Select a unit mounting system that provides adequate height
to allow for removal and disposal of frost and ice that will form
during the heating-defrost mode as well as allow installation of
condensate trap per requirements. Refer to Step 9 — Install Ex-
ternal Condensate Trap and Line – for required trap dimen-
sions.
ROOF MOUNT — Check building codes for weight distri-
bution requirements. Unit operating weight is shown in
Table 1.
10
D