Br (1-inch), br (1-inch) quick connect neutral, and qb (bolt-on) arc fault (af), ground fault (gf), dual function af/gf (df), and equipment protection (ep)

Advertisement

Instruction Leaflet IL003024EN
Effective December 2017
Trip
code
Description
4
Overvoltage
The breaker will trip if it experiences
voltage of 160 V rms or greater. The
breaker can be reset and the TEST
button can be pushed to verify that
the breaker is working properly.
Most likely caused by a loose or
oating neutral, either in the service
entrance or at the transformer.
5
Ground fault / grounded neutral
(DF and GF breakers only)
Current has found an alternate path
to ground, or the neutral and ground
are in contact downstream of the
breaker, this could cause harm to
people or property.
6
Self test failure
The breaker continually tests the
internal electronics and software
to ensure that the arc fault and
ground fault detection technology
is working properly. If the self-
diagnostics fail, the breaker will
trip. The built-in self-test features
will not allow the DF, AF, and GF
breakers to re-latch if it detects a
malfunction in the detection circuit.
Replace the breaker.
This Instruction Lea et applies to the following catalog numbers:
Ce feuillet d'instructions s'applique aux numéros de référence suivants :
Este folleto de instrucciones es aplicable a los siguientes números de catálogos:
Arc fault (AF)
Défaut d'arc électrique (AF)
Fallas de arco (AF)
BRN115AF
BRN115AFCS
BRN120AF
BRN120AFCS
BRHN115AF
BRHN120AF
QB1015CAF
QB1020CAF
QBH1015CAF
QBH1020CAF
Code de
déclenche-
ment
Description
4
Surtension
Le disjoncteur se déclenchera s'il
de valeur ef cace ou plus. Le
disjoncteur peut être réinitialisé et
le bouton TEST peut être appuyé
pour véri er que le disjoncteur
fonctionne correctement.
Cela est probablement causé par
un neutre défait ou ottant, soit
dans le coffret de branchement
ou dans le transformateur.
5
Défaut à la terre/neutre mis à la
terre (disjoncteurs GF et à double
fonction seulement)
Le courant a trouvé un autre
chemin vers la terre, ou le neutre
est en contact avec la terre en
aval du disjoncteur, ce qui pourrait
causer des blessures ou des
dommages.
6
Échec de l'auto-test
Le disjoncteur teste de manière
continue les composants
électroniques internes et le
logiciel pour s'assurer du bon
fonctionnement de la technologie
de détection de faute d'arc
électrique et de faute de mise à
la terre. Si les auto-diagnostics
échouent, le disjoncteur se
déclenchera. Les options d'autotest
intégré ne permettront pas aux
disjoncteurs AF, GF et à double
fonction de se réenclencher
s'ils détectent un mauvais
fonctionnement dans le circuit de
détection. Remplacer le disjoncteur.
AF/GF and dual function (DF)
Disjoncteurs AF , GF et à double fonction
AF/GF y función doble (DF)
BRAFGF115
BRN115DF
BRAFGF115CS
BRN120DF
BRAFGF115QN
BRHN115DF
BRAFGF120
BRHN120DF
BRAFGF120CS
QB1015AFGF
BRAFGF120QN
QB1020AFGF
BRHAFGF115
QBH1015AFGF
BRHAFGF115CS
QBH1020AFGF
BRHAFGF120
BRHAFGF120CS
BR (1-inch), BR (1-inch) quick connect neutral, and
QB (bolt-on) arc fault (AF), ground fault (GF), dual
function AF/GF (DF), and equipment protection (EP)
Código de
desconexión Descripción
4
Sobrevoltaje
El interruptor se desconectará
si experimenta un voltaje de
160 V RMS o superior. Se puede
restablecer el interruptor y
presionar el botón TEST (PRUEBA)
para veri car que el interruptor esté
funcionando correctamente.
Probablemente causada por un
cable neutro suelto o otante, ya
sea en la entrada de servicio o en
el transformador.
5
Falla a tierra/conductor neutro
conectado a tierra (Solamente
interruptores de DF y GF)
La corriente ha encontrado una ruta
alternativa a tierra o el conductor
neutro y la conexión a tierra están en
contacto aguas abajo del interruptor,
esto podría causar daño a las
personas o la propiedad.
6
Falla de la función de autoprueba
El interruptor comprueba
continuamente la parte electrónica
interna y el software para
asegurarse de que la tecnología de
detección de falla de arco y falla a
tierra funcione correctamente. Si el
autodiagnóstico falla, el interruptor
se desconectará. Las funciones
de autoprueba incorporadas no
permitirán que el interruptor de DF,
AF y GF vuelva a cerrarse si detecta
una falla en el circuito de detección.
Reemplace el interruptor.
Ground fault (GF)
Défaut à la terre (GF)
Fallas a tierra (GF)
BRN115GF
QB1020GF
BRN115GFCS
QB1025GF
BRN120GF
QB1030GF
BRN120GFCS
QB1020GFV
BRN125GF
QB1020GFX68
BRN125GFCS
QB1020EPV
BRN130GF
QB1015EP
BRHN115GF
QB1020EP
BRHN120GF
QBH1015GF
BRNH125GF
QBH1015GFV
BRHN130GF
QBH1020GF
QBH1025GF
QBH1030GF
QBH1015EP
QBH1020EP
EATON www.eaton.com
Canada
Canada
Canadá
BRN115AFC
BRN120AFC
BRAFGF115C
BRAFGF115CCS
BRAFGF120C
BRAFGF120CCS
BRN115DFC
BRN115DFCCS
BRN120DFC
BRN120DFCCS
BRN115GFC
BRN115GFCCS
BRN120GFC
BRN130GFC
7

Advertisement

loading

This manual is also suitable for:

Brafgf115Brn115dfBrn115gfQb1020gfBrn115afcBrn115afcs ... Show all