Broken Conductor Check Brcptoc (46); Measuring The Operate And Time Limit Of Set Values; Completing The Test; Directional Underpower Protection Guppdup (37) - ABB Relion 650 Series Commissioning Manual

Breaker protection
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 505 268-UUS A
7.3.13

Broken conductor check BRCPTOC (46)

Prepare the IED for verification of settings as outlined in section
settings".
Values of the logical signals for BRCPTOC (46) are available on the local HMI under Main menu/
Tests/Function status/Current/BRCPTOC(46,lub)/X:BRCPTOC. The Signal Monitoring in PCM600
shows the same signals that are available on the local HMI.
7.3.13.1

Measuring the operate and time limit of set values

1.
Check that the input logical signal BLOCK to the BRCPTOC (46) function block is logical zero
and note on the local HMI that the output signal TRIP from the BRCPTOC (46) function block
is equal to the logical 0.
2.
Set the measured current (fault current) in one phase to about 110% of the set operating
current
Observe to not exceed the maximum permitted overloading of the current circuits in the
terminal.
3.
Switch on the fault current and measure the operating time of BRCPTOC (46).
TRIP is controlled by Gate 13 in the configuration.
Use the TRIP signal from the configured binary output to stop the timer.
4.
Compare the measured time with the set value
5.
Activate the BLOCK binary input.
6.
Switch on the fault current (110% of the setting) and wait longer than the set value
No TRIP signal should appear.
7.
Switch off the fault current.
8.
Set the measured current (fault current) in same phase to about 90% of the set operating
current
9.
Switch on the fault current and wait longer than the set value
No TRIP signal should appear.
10.
Switch off the fault current.
7.3.13.2

Completing the test

Continue to test another function or end the testing by setting the parameter
Disabled under Main menu/Tests/IED test mode/1:TESTMODE. If another function is tested, then
set the parameter
BRCPTOC(46,lub)/X:BRCPTOC for the function, or for each individual function in a chain, to be
tested next. Remember to set the parameter
been tested.
7.3.14

Directional underpower protection GUPPDUP (37)

Prepare the IED for verification of settings as outlined in section
settings".
Values of the logical signals for GUPPDUP (37) are available on the local HMI under Main menu/
Tests/Function status/Current/GUPPDUP(37,P<)/1:GUPPDUP. The Signal Monitoring in PCM600
shows the same signals that are available on the local HMI.
Breaker protection REQ650
Commissioning manual
IP> .
IP> . Switch off the current.
Blocked to No under Main menu/Tests/Function test modes/Current/
© Copyright 2011 ABB. All rights reserved
"Preparing the IED to verify
tOper .
tOper .
Blocked to Yes , for each individual function that has
"Preparing the IED to verify
Section 7
Testing functionality
SEMOD175021-3 v5.1.1
SEMOD175021-7 v4
tOper .
SEMOD175021-42 v4
TestMode to
SEMOD175027-3 v5.1.1
61