Do you have a question about the Power Panel T30 and is the answer not in the manual?
Questions and answers
Summary of Contents for B&R Power Panel T30
Page 1
Power Panel T30 User's manual Version: 1.42 (November 2018) Model no.: MAPPT30-ENG Translation of the original documentation All values in this manual are current as of its publication. We reserve the right to change the contents of this manual without notice. B&R Industrial Automation GmbH is not liable for technical/editorial errors or incomplete information in this manual.
Page 2
Table of contents Power Panel T30 User's manual V1.42 - Translation of the original documentation...
3.6.2 Content of delivery..........................33 3.6.3 Technical data............................33 3.6.4 Temperature/Humidity diagram....................... 35 3.6.5 Dimensions.............................. 36 3.7 Connection elements............................ 38 3.7.1 Ethernet interface............................ 38 3.7.2 USB interfaces............................39 3.7.3 Power supply............................39 Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 4
6.6 OPC UA server............................. 94 6.6.1 Information model............................ 94 6.6.2 Description of the nodes of the information model................. 98 6.7 Touch keys as data points via OPC UA.....................123 Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 5
9.2.2 Requirements for immunity to disturbances..................133 9.2.3 Emission requirements.......................... 135 9.2.4 Mechanical conditions........................... 136 9.2.5 Electrical safety............................. 137 9.3 Underwriters Laboratories (UL)........................137 9.4 Det Norske Veritas - Germanischer Lloyd....................138 Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Added new chapter "Operating the Power Panel with a USB mouse". Updated "Technical data", "Automation Studio and Automation Runtime dependencies" and "Installation". 1.00 May 2015 Added new chapter "Automation Studio and Automation Runtime dependencies". Updated "Installation". Power Panel T30 User's manual V1.42 - Translation of the original documentation...
• Do not touch the connector contacts on the device (bus data contacts). • Do not touch the connector contacts on connected cables. • Do not touch the contact tips on circuit boards. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
• Electrical installation must be carried out in accordance with applicable guidelines (e.g. wire cross sections, fuses, protective ground connections). • Take the necessary protective measures against electrostatic discharge (see "Protection against electro- static discharge" on page Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Batteries and rechargeable batteries Cables Cardboard/Paper packaging Paper/Cardboard recycling Plastic packaging material Plastic recycling Table 1: Environmentally friendly disposal Disposal must take place in accordance with applicable legal regulations. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Contain useful information for users and instructions for avoiding malfunctions. Signal word Description Information: Useful information, application tips and instructions for avoiding malfunctions. Table 3: Organization of general notices Power Panel T30 User's manual V1.42 - Translation of the original documentation...
System characteristics 2 System characteristics The Power Panel T30 is equipped with an embedded browser and can also be used as a Visual Components client. The terminal series has 2 Ethernet and 2 USB interfaces as well as various configuration options.
System characteristics 2.3 Simple HMI The Power Panel T30 is a dedicated HMI device that can be operated in 2 different terminal modes: • Terminal as VNC client for VNC-based HMI applications created in Automation Studio with Visual Com- ponents.
1 Derivative: Sequential number [0...Z] Examples Power Panel T30, 4.3", landscape format. CPU and memory: 600 MHz (ARM Cortex-A8), 512 MB onboard flash drive. Display and touch screen: 4.3", 480 x 272 (WQVGA) resolution, analog resistive touch screen, landscape format, aluminum white pinstripe.
600 x 1024 043F 0573 0702 101G 043K 057L 070M 101N Model number 6PPT30.xxxx-20x 6PPT30.xxxx-20x Panel overlay Pinstripe pattern in aluminum white Pinstripe pattern in anthracite 6PPT30.xxxx-20W 6PPT30.xxxx-20B Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Device description • Type overview 3.1.1 Compare Power Panel T30 variants Format / Panel overlay Landscape format Portrait format Aluminum white Anthracite Aluminum white Anthracite Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Using a boot logo for Power Panels in portrait format 4.2.4 Using a boot animation in GIF format 4.3.2 AS ... Automation Studio, AR ... Automation Runtime, HW ... Hardware Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Cooling Passive LED status indicators Ethernet B&R ID code 0xE589 0xE58A 0xE58B 0xE58C Power button Reset button Buzzer Table: Power Panel T30 - 4.3" variants - Technical data Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 19
8 to 32 VDC Reverse polarity protection Electrical isolation Ethernet (ETH1/IF1 and ETH2/IF2) to other interfaces, power supply and ground Table: Power Panel T30 - 4.3" variants - Technical data Power Panel T30 User's manual V1.42 - Translation of the original documentation...
The internal fuse cannot be replaced by the user or reset. 3.3.4 Temperature/Humidity diagram Operation Operation Storage Storage Transport Transport Temperature [°C] Figure: Power Panel T30 - 4.3" variants - Temperature/Humidity diagram Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Mounting shield attachment plate for 4.3" Power Panel, page Dimensions of the installation cutout for this Power Panel variant: 130.8 ±1 mm x 86.8 ±1 mm See also "Installation cutout requirements" on page Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 22
Mounting shield attachment plate for 4.3" Power Panel, page Dimensions of the installation cutout for this Power Panel variant: 86.8 ±1 mm x 130.8 ±1 mm See also "Installation cutout requirements" on page Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Cooling Passive LED status indicators Ethernet B&R ID code 0xE58D 0xE58E 0xE58F 0xE590 Power button Reset button Buzzer Table: Power Panel T30 - 5.7" variants - Technical data Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 24
8 to 32 VDC Reverse polarity protection Electrical isolation Ethernet (ETH1/IF1 and ETH2/IF2) to other interfaces, power supply and ground Table: Power Panel T30 - 5.7" variants - Technical data Power Panel T30 User's manual V1.42 - Translation of the original documentation...
The internal fuse cannot be replaced by the user or reset. 3.4.4 Temperature/Humidity diagram Operation Operation Storage Storage Transport Transport Temperature [°C] Figure 1: Power Panel T30 - 5.7" variants - Temperature/Humidity diagram Power Panel T30 User's manual V1.42 - Translation of the original documentation...
112.9 13.8 42.8 12.5 Dimensions of the installation cutout for this Power Panel variant: 161.8 ±1 mm x 129.9 ±1 mm See also "Installation cutout requirements" on page Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 27
127.9 27.8 26.27 145.72 Dimensions of the installation cutout for this Power Panel variant: 129.9 ±1 mm x 161.8 ±1 mm See also "Installation cutout requirements" on page Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Cooling Passive LED status indicators Ethernet B&R ID code 0xE591 0xE592 0xE593 0xE594 Power button Reset button Buzzer Table: Power Panel T30 - 7.0" variants - Technical data Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 29
8 to 32 VDC Reverse polarity protection Electrical isolation Ethernet (ETH1/IF1 and ETH2/IF2) to other interfaces, power supply and ground Table: Power Panel T30 - 7.0" variants - Technical data Power Panel T30 User's manual V1.42 - Translation of the original documentation...
The internal fuse cannot be replaced by the user or reset. 3.5.4 Temperature/Humidity diagram Operation Operation Storage Storage Transport Transport Temperature [°C] Figure: Power Panel T30 - 7.0" variants - Temperature/Humidity diagram Power Panel T30 User's manual V1.42 - Translation of the original documentation...
13.8 42.8 138.9 12.5 Dimensions of the installation cutout for this Power Panel variant: 186.8 ±1 mm x 129.8 ±1 mm See also "Installation cutout requirements" on page Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 32
42.8 27.8 26.27 170.73 Dimensions of the installation cutout for this Power Panel variant: 129.8 ±1 mm x 186.8 ±1 mm See also "Installation cutout requirements" on page Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Cooling Passive LED status indicators Ethernet B&R ID code 0xE595 0xE596 0xE597 0xE598 Power button Reset button Buzzer Table: Power Panel T30 - 10.1" variants - Technical data Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 34
8 to 32 VDC Reverse polarity protection Electrical isolation Ethernet (ETH1/IF1 and ETH2/IF2) to other interfaces, power supply and ground Table: Power Panel T30 - 10.1" variants - Technical data Power Panel T30 User's manual V1.42 - Translation of the original documentation...
The internal fuse cannot be replaced by the user or reset. 3.6.4 Temperature/Humidity diagram Operation Operation Storage Storage Transport Transport Temperature [°C] Figure: Power Panel T30 - 10.1" variants - Temperature/Humidity diagram Power Panel T30 User's manual V1.42 - Translation of the original documentation...
158.03 145.8 60.56 26.19 Dimensions of the installation cutout for this Power Panel variant: 265.9 ±1 mm x 161.9 ±1 mm See also "Installation cutout requirements" on page Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 37
17.02 18.92 129.52 131.42 Dimensions of the installation cutout for this Power Panel variant: 161.9 ±1 mm x 265.9 ±1 mm See also "Installation cutout requirements" on page Power Panel T30 User's manual V1.42 - Translation of the original documentation...
External circuits connected to the device must be electrically isolated from the low voltage mains or from lethal voltages using reinforced or double insulation and must meet the requirements for SELV/ PELV circuits. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 40
Power Panel. Important! The ground connection of the device must be low impedance and connected to ground (e.g. grounding rail in the control cabinet) using a short path. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Only 2 screws are needed in order to adhere to the mechanical properties. For this reason, the cover of the Power Panel is installed using 2 screws when delivered. Some devices have unused drill holes that can be used for additional installation purposes (e.g. top-hat rail instal- lation). Power Panel T30 User's manual V1.42 - Translation of the original documentation...
2. Install the retaining clips on the device. To do this, insert the clips into the openings on the sides of the device (indicated by the orange circles). The number of openings may vary depending on the size of the device. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Power Panel. The minimum specified spacing is indicated in the following schematic diagrams. This applies to all Power Panel variants. Air circulation - Rear view >40 mm >40 mm Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 44
If the specified air circulation clearance values cannot be observed, then the internal housing temper- ature must be monitored by the user and appropriate measures taken if they are exceeded (see "Tem- perature monitoring" on page 91). Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 45
Commissioning • Installation Mounting shield attachment plate for 4.3" Power Panel Power Panel T30 User's manual V1.42 - Translation of the original documentation...
If the Power Panel is used in mounting orientations other than those indicated above, the application must monitor the temperature and take appropriate measures in the event of overtemperature. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
3 The grounding plate is installed directly on the de- vice with the available screws. Mounting shield attachment plate for 4.3" Power Panel, page Note: The image is valid for the 5.7" and 10.1" display variants. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 48
Power Panel T30 - 7.0" variant ① ② ① ② 1 Ground conductor 2 Unshielded lines Note: The image is valid for the 5.7" and 10.1" display variants. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
"ATEX Directive 2014/34/EU" on page 131. General safety guidelines Power Panel T30 devices are suitable for use in environments described in chapter "International and national certifications", section "ATEX Directive 2014/34/EU" on page 131. The wiring must be in accordance with the respective national regulations.
Page 50
Do not disconnect plugs with power applied or only in safe locations. The instructions in this section, including details regarding ATEX approval, can also be found on the information sheet delivered with the device. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
• The touch keys can also be queried using functions in library AsRfbExt Functions in the AsRfbExt library are described in Automation Help. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Starting touch screen calibration via the application Touch screen calibration can also be started via the application using an RFB function. See section "Starting touch screen calibration" on page Power Panel T30 User's manual V1.42 - Translation of the original documentation...
The mouse cursor automatically appears if a USB mouse is connected to the Power Panel. If the left and right mouse buttons are pressed simultaneously for more than 2 seconds, the Power Panel navigates to the service pages. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
In the next step, the Power Panel will be started in configured mode (see "Service page Startup" on page 58) regardless of whether an update is found or not. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 55
(see "Service page Backup & Reset" on page 81 "Service page Update" on page 77). Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 56
11 If the service page contains more elements than fit on the display, it is possible to scroll through the content using the up/down buttons. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Saving the Power Panel settings and closing/exiting the service page Save & Exit About & Info Information about the Power Panel (PPT system version, licenses for the About & Info software being used) Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Requirements and information about the boot logo and boot animation can be found in the following sections: • "Boot logo" on page 90 • "Boot animation" on page 90 Power Panel T30 User's manual V1.42 - Translation of the original documentation...
IP address can be obtained from the DNS server. For DNS functionality to be used, appropriate infrastructure must exist in the network. For more information, please contact your network administrator. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 60
Primary DNS server / Secondary DNS server / Tertiary DNS server Default setting: EMPTY The IP addresses for the DNS server. The input option for the DNS server is only displayed if option Activate DNS is enabled. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 61
Primary DNS server / Secondary DNS server / Tertiary DNS server Default setting: EMPTY The IP addresses for the DNS server. The input option for the DNS server is only displayed if option Activate DNS is enabled. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Default setting: (GMT) Dublin, Edinburgh, Lisbon, London When making a selection (via touch or mouse click), a list of all time zones is shown and the appropriate one can be selected. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
The options for the selected screen saver is described in the following section "Screensaver settings" on page (Button) Calibrate touch Function: Start touch calibration (see "Touch screen calibration" on page 52). (Button) Start demo Function: Show sample images Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 64
"Boot animation" on page Reasonable values range from 0 to the width/height of the screen. The screen width/height depends on the device being used and the configured Screen rotation. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 65
If the screensaver is started after a period of inactivity, the display goes into the selected mode: Black The display is dark. The backlight remains on. The display is dark. The backlight is switched off (result: lower power consumption). Backlight off Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Entry range: 10 to 500 Unit: ms (milliseconds) This setting is used to configure the duration of the generated audio signal. (Button) Test buzzer Function: Testing the buzzer (sound is produced). Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Enabled Input field Button key code is shown. Disabled A key code is not sent to the application. Information: The key code is only used for Web mode. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 68
KEY_e KEY_f KEY_g KEY_h KEY_i KEY_j KEY_k KEY_l KEY_m KEY_n KEY_o KEY_p KEY_q KEY_r KEY_s KEY_t KEY_u KEY_v KEY_w KEY_x KEY_y KEY_z Table: Upper and lower case letters Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 69
Accent (grave) KEY_F4 KEY_F5 KEY_BACKSLASH Backslash KEY_F6 KEY_F7 KEY_COMMA Comma KEY_F8 KEY_F9 KEY_DOT KEY_F10 KEY_F11 KEY_SLASH Slash KEY_F12 KEY_SPACE Space Table: Special keys, function keys, other keys, numbers Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 70
Paragraph character Circumflex ° Degree character µ Underline Greek letter µ (My) Left curly bracket · Interpunct Vertical bar ‰ Per mill Right curly bracket Table: Special characters Power Panel T30 User's manual V1.42 - Translation of the original documentation...
If no password has been entered, then the password will be queried each time a connection to the VNC server is established. The password is stored in configuration file PPTConfig.xml on the device. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 72
The VNC application is shown on the Power Panel screen in its original size. Information: Enabling option Enable local window scaling reduces the performance of the Power Panel because of increased demands on processing power. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
If the specified IP address is incomplete or a web server does not exist for the IP address or the spec- ified hostname, only the boot logo (if enabled) or the default animation for the web browser will be shown when establishing a connection to the web server. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 74
The virtual keyboard is created by the Power Panel system. If the web application (e.g. mapp View) contains its own on-screen keyboard, the virtual keyboard of the Power Panel should be disabled. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Default setting: Disabled Enabled The password is shown in the entry field as plain text. Disabled The password is hidden in the entry field using placeholder characters (●●●●●●). Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 76
Configuration • Service pages Encrypt password Default setting: Enabled Enabled The password is stored on the device in encrypted form. Disabled The password is stored on the device as plain text. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
They can be checked and modified on the service pages if necessary after loading and before saving the settings. Data is stored using functions on service page Save & Exit (see "Service page Save & Exit" on page 85). Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 78
"Boot logo" on page Boot animation PPTLogoA.gif (see "Boot animation" on page If a boot logo and/or a boot animation are already on the Power Panel, they will be overwritten. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 79
If the specified IP address is incomplete or a TFTP server does not exist for the IP address or the specified hostname, a message is output indicating that a network connection could not be established when attempting to connect fails during the update procedure. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 80
If the specified IP address is incomplete or an FTP server does not exist for the IP address or the specified hostname and therefore attempting to connect fails during the update procedure, a message is output indicating that a network connection could not be established. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
The settings made on the service pages are not saved and will be lost. Reset boot logo / animation (Button) Accessing this function resets the boot logo and the boot animation to the factory default settings (summary screen). Power Panel T30 User's manual V1.42 - Translation of the original documentation...
The password is hidden in the entry field using placeholder characters (●●●●●●). Encrypt password Default setting: Enabled Enabled The password is stored on the device in encrypted form. Disabled The password is stored on the device as plain text. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Identify token Audio Username Choose the identify token type Hand button User Password ●●●●●●●● OPC UA server password Storage max. 100 characters Update Show password Backup & Reset Security Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 84
Default setting: Disabled Enabled The password is shown in the entry field as plain text. Disabled The password is hidden in the entry field using placeholder characters (●●●●●●). Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Changes made are not saved and will be lost. The Power Panel starts as configured with the last settings that were saved (see "Service page Startup" on page 58). Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Version number of the PPT system (PPT image) Bootloader version Version number of the boot loader (Button) Show license Accessing this function displays the licenses of the software components used on the Power Panel. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
[Download to application memory]. The USB flash drive is reformatted and the following data is copied to the root directory: ° PPTImage.img.gz ° PPTImage.md5 ° PPTConfig.xml ° PPTLogo.bmp.gz ° PPTLogoA.gif Power Panel T30 User's manual V1.42 - Translation of the original documentation...
The PPT system (PPT image) can be used to update any Power Panel. The boot logo and configuration (settings), on the other hand, can only be used on the same devices. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Videos can be displayed in web mode (see "Configuring web mode" on page 73). The following container formats are supported when embedding videos into a web-based HMI application: • WebM Power Panel T30 User's manual V1.42 - Translation of the original documentation...
The boot animation is superimposed over an existing static boot logo. The boot animation is only displayed when starting Web or VNC mode. It is not displayed while the device is booting. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
43), it makes sense for the application to monitor the Power Panel temperature. The application can take appropriate corrective measures if a certain temperature is exceeded. Important! The temperature within the housing is not permitted to exceed 85°C. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
"Configuration" on page 54). Information: Emitting an audible tone with beep is always done independent of the setting on service page Audio (see "Service page Audio" on page 66). Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Verdana, Regular Times New Roman Liberation Serif, Regular Courier New Liberation Mono, Regular "serif", "sans-serif" and "monospace" are "generic" fonts. 16 px is set as the default font size. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
The node identifiers are partly specified in the OPC UA specification or by B&R. A namespace therefore specifies which institution defined the node (naming authority) and is listed in the form of a namespace URI. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 95
These nodes provide variables/parameters for reading information from the device. Property Device-specific properties of the device are read out via these nodes in order to be able to identify the device. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 96
Value attribute of the node can be changed. Information: The changes to the system settings that were made with the parameters above are only saved with method SaveConfiguration. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 97
ParameterSet, MethodSet Device properties into logical function groups. The detailed description of the nodes in the following section is structured according to this logical structure. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
6.6.2.1.3 MemoryAvailable Available RAM in MB. Path to the node (BrowsePath) Path: 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/2:ParameterSet/4:MemoryAvailable Alternative path (function group): 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/3:Diagnostics/4:MemoryAvailable Node attribute NodeClass Variable DataType UInt16 AccessLevel CurrentRead UserAccessLevel CurrentRead Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 99
Entire RAM of system in MB. Path to the node (BrowsePath) Path: 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/2:ParameterSet/4:MemoryTotal Alternative path (function group): 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/3:Diagnostics/4:MemoryTotal Node attribute NodeClass Variable DataType UInt16 AccessLevel CurrentRead UserAccessLevel CurrentRead Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 100
Path to the node (BrowsePath) Path: 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/2:ParameterSet/4:BuzzerSource Alternative path (function group): 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/3:Configuration/4:Audio/4:BuzzerSource Node attribute NodeClass Variable DataType BrBuzzerSource (Enumeration) AccessLevel CurrentRead, CurrentWrite UserAccessLevel CurrentRead, CurrentWrite Data type BrBuzzerSource (enumeration) Value String Touch Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 101
"Buzzer duration" on page 66 Path to the node (BrowsePath) Path: 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/2:ParameterSet/4:BuzzerDuration Alternative path (function group): 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/3:Configuration/4:Audio/4:BuzzerDuration Node attribute NodeClass Variable DataType UInt16 AccessLevel CurrentRead, CurrentWrite UserAccessLevel CurrentRead, CurrentWrite Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 102
"Open service page" on page 67 Path to the node (BrowsePath) Path: 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/2:ParameterSet/4:OpenServicePage Alternative path (function group): 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/3:Configuration/4:HandButton/4:OpenServicePage Node attribute NodeClass Variable DataType Boolean AccessLevel CurrentRead, CurrentWrite UserAccessLevel CurrentRead, CurrentWrite Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 103
Path: 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/2:ParameterSet/4:NetworkMode Alternative path (function group): 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/3:Configuration/4:Network/4:NetworkMode Node attribute NodeClass Variable DataType BrNetMode (Enumeration) AccessLevel CurrentRead, CurrentWrite UserAccessLevel CurrentRead, CurrentWrite Data type BrNetMode (enumeration) Value String DHCPClient StaticIP Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 104
Path to the node (BrowsePath) Path: 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/2:ParameterSet/4:PrimaryDNS 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/2:ParameterSet/4:SecondaryDNS 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/2:ParameterSet/4:TertiaryDNS Alternative path (function group): 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/3:Configuration/4:Network/4:PrimaryDNS 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/3:Configuration/4:Network/4:SecondaryDNS 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/3:Configuration/4:Network/4:TertiaryDNS Node attribute NodeClass Variable Datentyp String AccessLevel CurrentRead, CurrentWrite UserAccessLevel CurrentRead, CurrentWrite Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 105
"Subnet mask / Default gateway" on page 61 Path to the node (BrowsePath) Path: 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/2:ParameterSet/4:DefaultGateway Alternative path (function group): 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/3:Configuration/4:Network/4:DefaultGateway Node attribute NodeClass Variable Datentyp String AccessLevel CurrentRead, CurrentWrite UserAccessLevel CurrentRead, CurrentWrite Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 106
"Screensaver" on page 63 Path to the node (BrowsePath) Path: 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/2:ParameterSet/4:EnableScreensaver Alternative path (function group): 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/3:Configuration/4:Screen/4:EnableScreensaver Node attribute NodeClass Variable DataType Boolean AccessLevel CurrentRead, CurrentWrite UserAccessLevel CurrentRead, CurrentWrite Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 107
Path: 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/2:ParameterSet/4:ScreensaverType Alternative path (function group): 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/3:Configuration/4:Screen/4:ScreensaverType Node attribute NodeClass Variable DataType BrScreensaver (Enumeration) AccessLevel CurrentRead, CurrentWrite UserAccessLevel CurrentRead, CurrentWrite Data type BrScreensaver (enumeration) Value String Black BacklightOff Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 108
"Boot logo or boot animation" on page 58 Path to the node (BrowsePath) Path: 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/2:ParameterSet/4:ShowBootLogoVNC 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/2:ParameterSet/4:ShowBootLogoWeb Alternative path (function group): 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/3:Configuration/4:Startup/4:ShowBootLogoVNC 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/3:Configuration/4:Startup/4:ShowBootLogoWeb Node attribute NodeClass Variable DataType Boolean AccessLevel CurrentRead, CurrentWrite UserAccessLevel CurrentRead, CurrentWrite Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 109
• UserMemoryShare → Option Allow access to user memory via network Path to the node (BrowsePath) Path: 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/2:ParameterSet/4:USBMemoryShare 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/2:ParameterSet/4:USBMemoryShare Alternative path (function group): 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/3:Configuration/4:Storage/4:UserMemoryShare 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/3:Configuration/4:Storage/4:UserMemoryShare Node attribute NodeClass Variable DataType Boolean AccessLevel CurrentRead, CurrentWrite UserAccessLevel CurrentRead, CurrentWrite Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 110
Service page Time → NTPServer1 Path to the node (BrowsePath) Path: 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/2:ParameterSet/4:NTPServer1 Alternative path (function group): 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/3:Configuration/4:Time/4:NTPServer1 Node attribute NodeClass Variable Datentyp String AccessLevel CurrentRead, CurrentWrite UserAccessLevel CurrentRead, CurrentWrite Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 111
"Enable local window scaling" on page 72 Path to the node (BrowsePath) Path: 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/2:ParameterSet/4:VNCLocalWindowScaling Alternative path (function group): 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/3:Configuration/4:Vnc/4:VNCLocalWindowScaling Node attribute NodeClass Variable DataType Boolean AccessLevel CurrentRead, CurrentWrite UserAccessLevel CurrentRead, CurrentWrite Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 112
"Virtual keyboard" on page 74 Path to the node (BrowsePath) Path: 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/2:ParameterSet/4:VirtualKeyboardWeb Alternative path (function group): 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/3:Configuration/4:Web/4:VirtualKeyboardWeb Node attribute NodeClass Variable DataType Boolean AccessLevel CurrentRead, CurrentWrite UserAccessLevel CurrentRead, CurrentWrite Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 113
0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/3:Control/4:BuzzerWithPara Arguments for method call Argument Data type Name Description UInt32 Frequency Frequency of the buzzer in hertz [Hz]. UInt32 Duration Duration of the buzzer in milliseconds [ms]. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 114
Arguments for method call Argument Data type Name Description UInt32 Brightness Brightness in percent [%]. Range of values: 0 - 100 Scaling 0 → 20% to 100 → 100% Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 115
Service page Update → Update settings / boot logo / system (Button) Path to the node (BrowsePath) Path: 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/2:MethodSet/4:StartUpdate Alternative path (function group): 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/3:Control/4:StartUpdate Arguments for method call Arguments Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 116
Inner temperature of the Power Panel: See "Temperature monitoring" on page Path to the node (BrowsePath) Path: 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/2:ParameterSet/4:Temperature1 Alternative path (function group): 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/3:Status/4:Temperature1 Node attribute NodeClass Variable DataType Float AccessLevel CurrentRead UserAccessLevel CurrentRead Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 117
Path: 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/2:ParameterSet/4:Keys/4:Key127 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/2:ParameterSet/4:Keys/4:Key126 Alternative path (function group): 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/3:UserInterface/4:Keys/4:Key127 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/3:UserInterface/4:Keys/4:Key126 Node attribute NodeClass Variable DataType BrKeyState (Enumeration) AccessLevel CurrentRead UserAccessLevel CurrentRead Data type BrKeyState (enumeration) Value String Released Pressed Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 118
The value of DeviceRevision is identical to the value of HardwareRevision Path to the node (BrowsePath) Path: 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/2:DeviceRevision Alternative path (function group): 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/2:Identification/2:DeviceRevision Node attribute NodeClass Variable DataType String AccessLevel CurrentRead UserAccessLevel CurrentRead Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 119
B&R ID code (see technical data of the device). Path to the node (BrowsePath) Path: 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/3:ProductCode Alternative path (function group): 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/2:Identification/3:ProductCode Node attribute NodeClass Variable DataType UInt32 AccessLevel CurrentRead UserAccessLevel CurrentRead Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 120
Software version of the PPT system: e.g. 1.2.0 Path to the node (BrowsePath) Path: 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/2:SoftwareRevision Alternative path (function group): 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/2:Identification/2:SoftwareRevision Node attribute NodeClass Variable DataType String AccessLevel CurrentRead UserAccessLevel CurrentRead Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 121
Description B&R B&R ≥2 Customer ID Path to the node (BrowsePath) Path: 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/3:VendorId Alternative path (function group): 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/2:Identification/3:VendorId Node attribute NodeClass Variable DataType UInt32 AccessLevel CurrentRead UserAccessLevel CurrentRead Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 122
Path to the node (BrowsePath) Path: 0:Root/0:Objects/2:DeviceSet/4:PowerPanelT30/2:DeviceManual Device property CompatibilityId is only available as a property of node PowerPanelT30 . Node attribute NodeClass Variable DataType String AccessLevel CurrentRead UserAccessLevel CurrentRead Power Panel T30 User's manual V1.42 - Translation of the original documentation...
State of the Hand button. Key is pressed. Key is not pressed. DINT Touch area outside the display and the Hand button. Key is pressed. Key is not pressed. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Cleaning the label on the back of the unit is only permitted with a dry cloth. This ensures readability of the thermal print during the service life of the device. Information: The display with the touch screen should be cleaned at regular intervals. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
• Line type: Can result in permanent damage. What causes image persistence? • Static images • No screensaver • Sharp transitions in contrast (e.g. black/white) • High ambient temperatures • Operation outside of specifications Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 126
• Constantly switching between static and dynamic images • Avoiding excessive brightness differences between foreground and background elements • Using colors with similar brightness • Using complementary colors in consecutive images • Using screensavers Power Panel T30 User's manual V1.42 - Translation of the original documentation...
B&R POWERLINK cables can be used for the Ethernet connections. These cables are suitable for networks with transfer rates up to 100 Mbit/s, but not for Gigabit networks. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
For technical data and additional information about cables, see the corresponding documentation. This can be lo- cated and downloaded by searching for the cable's model number on the B&R website at www.br-automation.com. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Explosion protection (ATEX) Notified bodies Europe (EU) Underwriters Laboratories Inc. (UL) Canada (certification for Canada and USA) Det Norske Veritas - Ger- Germany DNV GL manischer Lloyd (DNV GL) Norway Power Panel T30 User's manual V1.42 - Translation of the original documentation...
For information about the versions of applicable standards, see the declaration of conformity. Declaration of conformity Website > Downloads > Certificates > Declarations of conformity > Declaration of conformity HMI IPC Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 131
Declaration of conformity Website > Downloads > Certificates > Declarations of conformity > Declaration of conformity ATEX Power Panel T30 Certificate (type approval certificate) Website > Downloads > Certificates > ATEX > Power T30...
- Part 6-4: Generic standards - Emission standard for industrial environments Programmable logic controllers EN 61131-2 - Part 2: Guidance for inspection and routine testing Replacement for EN 60068-2-32 Power Panel T30 User's manual V1.42 - Translation of the original documentation...
±2 kV / 5 kHz Criteria B Other I/Os and interfaces ±1 kV / 5 kHz Criteria B Only for connections with a permitted line length greater than 3 m. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 134
DC power inputs 0% residual voltage ≥10 ms (PS2) 20 attempts Criteria A Mains frequency per manufacturer data Use of a B&R power supply guarantees that these requirements are met. Power Panel T30 User's manual V1.42 - Translation of the original documentation...
76 dB (µV/m) peak value 56 dB (µV/m) average value 3 to 6 GHz 80 dB (µV/m) peak value 60 dB (µV/m) average value Depending on highest internal frequency Power Panel T30 User's manual V1.42 - Translation of the original documentation...
10 to 40 kg 0.3 m 20 to 100 kg 0.25 m >40 kg 0.25 m >40 kg 0.25 m >100 kg 0.1 m 5 attempts Replacement for EN 60068-2-32 Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Safety requirements for electrical equipment for measurement, control and laboratory use - Part 2-201: Particular requirements for control equipment Certificate Website > Downloads > Certificates > UL > Power Panel Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Environmental test specification for electrical, electronic and programmable equipment and systems. Certificate Website > Downloads > Certificates > Maritime > DNV GL > X20 / Power Panel T/C > DNV GL Type Approval Certificate Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 139
Publishing information Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Page 140
Publishing information Publishing information B&R Industrial Automation GmbH B&R Strasse 1 5142 Eggelsberg Austria Telephone: +43 7748 6586-0 Fax: +43 7748 6586-26 office@br-automation.com Power Panel T30 User's manual V1.42 - Translation of the original documentation...
Need help?