Air Guide Work - LG MULTI V S ARUV040GSR0 Installation Manual

Table of Contents

Advertisement

1,MFL67798026,영영 19. 3. 14. 영영 4:48 Page 17
Seasonal wind and cautions in winter
• Sufficient measures are required in a snow area or severe cold area in winter so that product
can be operated well.
• Get ready for seasonal wind or snow in winter even in other areas.
• Install a suction and discharge duct not to let in snow or rain.
• Install the outdoor unit not to come in contact with snow directly. If snow piles up and freezes
on the air suction hole, the system may malfunction. If it is installed at snowy area, attach the
hood to the system.
• Install the outdoor unit at the higher installation console by 50cm than the average snowfall (an-
nual average snowfall) if it is installed at the area with much snowfall.
• Where snow accumulated on the upper part of the Outdoor Unit by more than 10cm, always
remove snow for operation.
- The height of H frame must be more than 2 times the snowfall and its width shall not ex-
ceed the width of the product. (If width of the frame is wider than that of the product,
snow may accumulate)
- Don't install the suction hole and discharge hole of the Outdoor Unit facing the seasonal
wind.

Air guide work

In case of out door unit is located outdoor cabin of apartment or flats, then the efficiency can
drop and system pressure increases thus finally damaging the compressor or other components
in the system by heat short circuit.
• Do not use bended louver. It disturbs the air circulation.
• The opening ratio is at least 80%
• Louver angle is 0-20 degree
• Louver pitch will be as more than 100mm
• If you have a insect control net, consider the shielded area and static pressure loss
• Check the static pressure range of outdoor unit fan.
Then, install air guide in the range of static pressure.
Secure minimum intake area
When the intake area is not secured can efficiency drop and products may not be operating
• Minimum intake area (For reference)
Model
Minimum
intake area (m
Intake
300mm or more
150mm or
area
350mm
more
or more
Air guide duct
Air guide
ARUV025GSR0
ARUV030GSR0
ARUV040GSR0
ARUV050GSR0
0.7
2
)
INSTALLATION SPACE
Less than
Less than
Less than
20 degrees
20 degrees
20 degrees
Louver pitch
Louver pitch
Louver pitch
100 mm or more
100 mm or more
100 mm or more
Wind speed : Vs ≤ 1.5 m/s
ARUV060GSR0
1.2
17

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents