Labvision; Bms - Jakka Control Kit 4 Manual

Heat recovery unit controller
Table of Contents

Advertisement

JAKKA Control Kit 4
5.1.3

Labvision

This is the final screen after the test.

5.2 BMS

BMS is Building Manage System connected with 3 lines BMS, Unit, Season.
Labvision is used to check if all variables are correct project F2 MN. Follow points to test the BMS. Which heater are
on with difference of Set Point Room or Indoor sensor. The best way is set Heater config to INDOOR and change Set
point on RC.
MASTER
BMS
ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
*Check the heater relays!
www.jakkagroup.com
UNIT
SEASON
OFF
HEAT
OFF
HEAT
OFF
COOL
ON
COOL
COOL is blinking, LED is on, input fan speed possible
ON
HEAT
HEAT is blinking, LED is on, input fan speed possible
ON
HEAT
Result
No BMS, Modbus is on
HEAT is blinking
COOL is blinking
HEAT is on, LED is off, fan speed purge
Manual
22