SUPPLY FAN
HI
MED
LOW
Negative Offset
Supply Fan is adjusted because the limit of the fan MAX and MIN is reaches.
Negative Offset is Supply Fan LOW = Exhaust Fan + Offset
Positive Offset is Supply Fan HI = Exhaust Fan - Offset
The fan settings for LOW, MED, HI speed are applicable for the supply fan speed, in case of an offset the supply speed
is used as reference to correct the exhaust fan speed.
When VOD (§ 2.1.5) is selected the target fan speed applies to supply fan and is used as reference to adjust the exhaust
fan with an offset. The offset also applies to the minimum and maximum fan speed settings in such a way that always
an offset remains,
2.5.2.1

Conditions

There are several conditions for the fan balancing:
Exhaust_Fan_MAX
Exhaust_Fan_MAX
Exhaust_Fan_MAX
Exhaust_Fan_MIN
Exhaust_Fan_MIN
Supply_Fan_MAX
Supply_Fan_MAX
Supply_Fan_MIN
Supply_Fan_MIN
Supply_Fan_MIN
VOD_MAX_Fan_speed <= Exhaust_Fan_MAX
VOD_MIN_Fan_speed >= Exhaust_Fan_MIN
2.5.3

Parameters

Parameter
Room_Setpoint
Exhaust_Fan
Exhaust_Fan_MIN
Exhaust_Fan_MED
Exhaust_Fan_MAX
Supply_Fan
Supply_Fan_MIN
Supply_Fan_MED
Supply_Fan_MAX
Operation_Mode
Temp_MAX_Outdoor_Cooling
Temp_MIN_Outdoor_Cooling
Temp_MAX_Outdoor_Heater
Temp_MIN_Outdoor_Heater
Temp_AUTO_Season
Temp_HYST_UP_Season
Temp_HYST_DOWN_Season
Heater1_config
Heater2_config
Heater3_config
Heaters_config
Heaters_Hysterese
VOD_MIN_Fan_speed
VOD_MAX_Fan_speed
Offset_Supply_Exhaust_Air
BMS heater post purge time
Filter_check_time
11
EXHAUST FAN
OFFSET
HI
MED
LOW
Positive Offset
>
90
<= 255
>= 90
<= 255
<
Exhaust_Fan_MAX
>
90
<= 255
>= 90
<
255
<
Supply_Fan_MAX
SUPPLY FAN
EXHAUST FAN
OFFSET
HI
MED
LOW
Unit
Default
Range
ºC
20
10..40
170
90..255
90
90..255
170
90..255
255
90..255
170
90..255
90
90..255
170
90..255
255
90..255
0
ºC
32
10..40
ºC
10
10..40
ºC
35
10..40
ºC
15
10..40
ºC
25
10..40
ºC
0
10..40
ºC
4
10..40
KW
1
1..255
KW
2
1..255
KW
5
1..255
1
1
250
90..255
100
90..255
0
-10..10
second
120
10-255
hours
1200
10..255
JAKKA Control Kit 4
HI
MED
LOW
Reference §
2.1.2
2.1.1
2.1.1
2.1.1
2.1.1
2.1.1
2.1.1
2.1.1
2.1.1
0..5
2.1
2.1.2
2.1.2
2.1.3
2.1.3
2.1.4
2.1.4
2.1.4
2.1.3.3
2.1.3.3
2.1.3.3
0..1
2.1.3.3
1..2
2.1.3.3
2.1.5
2.1.5
2.5.2
2.2
2.3
www.jakkagroup.com