Jakka EVO PH Manual

Jakka EVO PH Manual

Heat recovery unit controller

Advertisement

Manual
EVO PH and EVO D PH-IP
Heat recovery unit controller
JAK-KA GROUP
J.8.Г
december
2019
www.jakkagroup.com

Advertisement

Table of Contents
loading

Summary of Contents for Jakka EVO PH

  • Page 1 Manual EVO PH and EVO D PH-IP Heat recovery unit controller JAK-KA GROUP J.8.Г december 2019 www.jakkagroup.com...
  • Page 2: Table Of Contents

    Mounting ....... 30 Jakka Group se trudi da redovno ažurira tehničke podatke, opise i fotografije u katalozima i uputstvima, kao i cene u cenovnicima, ali ne možemo da garantujemo da su sve objavljene informacije kompletne i tačne. Stoga Vas molimo, u cilju bolje saradnje, da pre konačne odluke proverite podatke sa našim prodavcima, kako bismo izbegli greške.
  • Page 3: Main Window

    EVO controller Manual MAIN WINDOW The touch-screen control panel has been designed to control Controlled Mechanical Ventilation units with Heat Return (VMC-RC) in a simple and intuitive way. The user controls the unit by slightly pressing the graphic display icons; the arrow keys that appear after pressing a changeable parameter enable the user to interact with the unit by scrolling menu items and changing values.
  • Page 4: Booster Function

    EVO controller Manual Changing air flow Changing fan speed as a percentage Turning off Changing pressure In detail, the possible options are as follows: - off: fans are motionless with this option, but watch out that the unit is live anyway; this value is achieved by going below the minimum speed value that can be set;...
  • Page 5: Air Post-Treatment Control

    EVO controller Manual SET POINT TEMPERATURE The temperature set-point is given by the thermometer icon (located at the bottom right of the screen like images next paragraph) that can be red (heat mode) or blue (cooling mode). When the bottom icon is selected, the desired interior temperature set-point (Ts) function is accessed: the user can increase the Ts value by the up arrow key or, vice versa, reduce it by the down arrow key.
  • Page 6: Post Heating Control

    EVO controller Manual PRE-HEATING CONTROL In addition to post-heating, the EVO-PH control can run an electric pre-heating system to prevent the formation of ice in the heat exchanger. The control starts the anti-frost procedure automatically when the temperature detected by the expelled probe (Tx) drops below 3°C.
  • Page 7: Status Menu: Operating Status

    EVO controller Manual STATUS MENU: OPERATING STATUS If the remote control panel is used to run several units (master-slave mode), a screen will be displayed in the menu with the list of available machines (max 4): Selection of units to be monitored, Display of the Status menu with fan speed master/slave configuration In order to display the status of one unit, you must select this unit (move by means of the arrow keys and confirm your selection by...
  • Page 8 EVO controller Manual Fan supply Supply fan speed value, which is expressed in: - revolutions per minute (RPMs) if fans with tachometric signal are installed; - percentage if variable speed fans without tachometric signal are installed (Off when the fan is off); - Off, 1 ,2 or 3 for 3-speed fans.
  • Page 9 EVO controller Manual It is on if one digital input (DI) is configured as booster (this parameter can be set in the Boost factory): - end the DI is open and a longer time than Boost min. has lapsed after the last change of DI status (from closed to open), booster off (fans at the speed set by the control);...
  • Page 10: Program Menu Weekly Program Control

    EVO controller Manual PROGRAM MENU: WEEKLY PROGRAM CONTROL This menu controls the fan speed (on three levels), which is expressed as a percentage for variable speed machines (or full-scale pressure or flow machines without cop/cav kit), in pascal for constant pressure machines, and in m3/h for constant flow machines with kit.
  • Page 11: Default

    EVO controller Manual DEFAULT When this menu item is selected and OK is pressed, unit control parameters are automatically assigned default values: Program valid Monday through Friday TIME TABLE Time period Fan speed/flow/pressure Air after-treatment status: (ON / OFF) Medium 00:00 ->...
  • Page 12 EVO controller Manual In order to change the settings of each day, just select the day in the summary display window and press OK; now, the detail screen of the selected day is displayed with the list of the eight possible time periods (C1 C8), while the selected day of the week is displayed in the top left corner of the screen.
  • Page 13: Setting Speed Levels

    EVO controller Manual Copy day: selecting the day to be copied Selecting the copy day function After accessing the Copy day page (as displayed in the top left corner of the screen), you can select the day you want to copy the program from using the arrow keys to scroll the various days.
  • Page 14: Alarms

    EVO controller Manual ALARMS MENU: DISPLAY OF THE ALARM STATUS If the control detects an abnormal status, the latter is indicated in the main control screen by a specific flashing icon and a red writing at the top of the screen (Call service o DirtyFilters). If the alarm is detected when the screen is in stand-by mode, the display flashes at about 10-second intervals.
  • Page 15 EVO controller Manual The return air temperature sensor works properly Tr (return) Problem with the return air temperature sensor: check electrical connections of the temperature probe (see wiring diagram); 2) if the problem is not solved, replace the temperature probe 3) if the problem is not solved, replace the electronic card.
  • Page 16 EVO controller Manual It is present only if the fan speed control is configured with an external 0-10V analog signal (Installer menu) The external signal source works properly Ext.signal External signal not present (voltage at the clamps = 0V): 1) check electrical connections of the external source (see electric diagram); 2) if the problem is not solved, check whether the external signal is present (tester) and its value is greater than 0V;...
  • Page 17: Setting User Parameters

    EVO controller Manual PARAMETERS MENU: SETTING USER PARAMETERS By parameters menu it is possible to set the current season for the management of the by-pass . The control automatically adjusts regulations basing, as regards the by-pass, on the external temperature, return and the selected season. If a dehumidification system is installed, it is possible, in this menu, to enable\disable it and set the relative humidity threshold value for activation.
  • Page 18 EVO controller Manual PARAMETERS AVAILABLE IN THE INSTALLER MENU Language With this parameter, you can select the language of all menus (except for the Factory menu, which will always be in English). English language (default) French language Spanish language Italian language Dutch language German language Hungary language...
  • Page 19 EVO controller Manual The fan speed will be controlled by a relative humidity (RH) sensor with 0-10V output and will have a linear trend UR sensor between 0 and 100% RH (0V corresponds to 0% RH and 10V corresponds to 100% RH); if the external signal of the RH sensor takes the 0V value, the control will display a problem with the sensor.
  • Page 20 EVO controller Manual None (Default value) no device is installed for the automatic operation of the fan speed. This parameter is only available if the auto parameter is set on ext. signal or UR sensor. It can take values between AutoMin % 0 and 99% (1% steps) with the following limit: AutoMin%<AutoMax% For a unit equipped with variable speed fans: If auto ext.
  • Page 21 EVO controller Manual AutoOff ppm This parameter is only available if the auto parameter is set on CO VOC and the digital output is configured as 0000->2000 auto cmp (Factory menu). Default value 0500, it is expressed in ppm; for higher values of ppm as read by the CO probe than the set one, the digital output dedicated returns to its standard status.
  • Page 22 EVO controller Manual This parameter is only available for constant flow units with control on both flows (Factory menu). (default 030) It Tau Flow Ex s is the value of the integral time relevant to the return flow. This parameter is only available for constant pressure units with control on one flow (Factory menu). (default 040) Kp Flow It is the value of the proportional coefficient relevant to the detected flow.
  • Page 23 EVO controller Manual Default value 0. It represents the percentage speed value of the fans to be added to the one set to obtain the DFans desired increase during dehumidification. For example, if the fan speed is 20% and this parameter is set to 30%, 000%->100% when the dehumidification is enabled, the speed changes to 50% (20 + 30).
  • Page 24: Modbus Interaction Table

    EVO controller Manual Decrease / increase buttons Fans speed Output Temperature Recovery Temperature Expulsion Input Temperature Temperature By-pass Decrease / Increase 10 units Decrease / Timer Increase 1 unit Main web server screen On the main mask we find a reproduction of the classic touch panel screen, the difference are the changes that are performed using the arrow keys.You can increase or decrease the values by one unit clicking the single-arrow key, otherwise you can increase or decrease them by several units clicking the double-arrow key.
  • Page 25 EVO controller Manual ADDRESS WORD ID FORMAT VALUE DESCRIPTION WHEN SWITCHING THE UNIT ON OR OFF CONFIGURATION SW MODEL SW_PN_0 SW TYPE 0 SW MODEL SW_PN_1 SW TYPE 1 SW VERSION SW_PN_2 SW VER 0 (AAMM) SW VERSION SW_PN_3 SW VER 1 (DDPP) B00: R/W DEVICE_RESET (1=RESET) PCB RESET NOTICE BIT: REMOTE...
  • Page 26 EVO controller Manual TEMPERATURE TEMPERATURE SET POINT (IF AIR POST-TREATMENT IS PRESENT OFF(0) or 50-300 (0,1 °C) SET_POINT** ONLY) 0-14400 (sec.) MAXIMUM FAN SPEED TIMER SPEEDS B00-06: REMOTE_SUPPLY_SPEED PARAMETER 0-100% TO COMMAND INDEPENDENTLY FANS SPEED FROM THE REMOTE B07: SUPPLY_SPEED_REMOTE_CONTROL LOGIC CONTROL .
  • Page 27 EVO controller Manual B08: COMM_X531_FAIL COMMUNICATION ERROR IN X531 BOARD. B09: TW_FAIL WATER COIL FROST ALARM. B10: TW_LOW B11: AUTO_TO_FAIL AIR/HUMIDITY QUALITY PROBE TIMEOUT ALARM. B12: COMM_X570_DPE_FAIL COMMUNICATION ERROR IN X570 BOARD DELIVERY. B13: COMM_X570_DPE_FAIL COMMUNICATION ERROR IN X570 BOARD EXHAUST. B14: DPSUPPLY_FAIL DELIVERY PRESSURE SENSOR FAILURE.
  • Page 28: Installation

    EVO controller Manual SERVICE-DATA (100 bit/s) DEFAULT = 96 8502 BAUD RATE* DISCONNECTION TIME DEFAULT = 10 SEC. TIME OUT* (SEC) 8503 65535 DISABLES DISCONNECTION IN CASE OF FAILURE TO READ REGISTERS DAY * ** 8555 1 (MONDAY) -7 (SUNDAY) SET DAY 8556 HOUR * **...
  • Page 29: Terms Of Guarantee

    EVO controller Manual CONTROL CHARACTERISTICS Power: 9 / 30 VDC 250mW, operating temperature between 0° and 50 °C; storage temperature between -20 °C and 70 °C. TERMS OF GUARANTEE The two-year (24-month) guarantee period starts from the receipt of the equipment: the date of receipt must be indicated in the purchase invoice.
  • Page 30: Mounting

    EVO controller Manual MOUNTING (mm) Insert two sticks in the left and the right of the touch panel Insert bottom touch panel in the support Press the support up and the touch panel down then insert also the top touch panel in the support www.jakkagroup.com...
  • Page 31 JAK-KA GROUP - SRBIJA adresa: Bulevar Zorana Đinđića 80 11070 Novi Beograd, Srbija telefon: +381 (0)11 2 600 901 faks: +381 (0)11 2 600 906 web: www.jakkagroup.com e-mail: jakkagroup@jakkagroup.com JAK-KA GROUP - CRNA GORA adresa: V Crnogorske brigade 3 85347 Igalo, Crna Gora telefon: +382 (0)31 330 285 faks: +382 (0)31 330 285 mobilni: +382 (0)69 517 008...