RC display ......Jakka Group se trudi da redovno ažurira tehničke podatke, opise i fotografije u katalozima i uputstvima, kao i cene u cenovnicima, ali ne možemo da garantujemo da su sve objavljene informacije kompletne i tačne. Stoga Vas molimo, u cilju bolje saradnje, da pre konačne odluke proverite podatke sa našim prodavcima, kako bismo izbegli greške.
JAKKA Control Kit 4 Manual 1 General The control has the following specifications Power Supply 230VAC (-15%, +10%) 50Hz (± 2%) Ambient Functional 0 to +60C (32°F to 140°F (Peak temperatures, not Temperature Storage continuous) (-25 to +75°C) (-13°F to 167°F) Humidity 93% RV at 25°C (77°F)
JAKKA Control Kit 4 Manual 2 Control Functions By-pass The heat recovery unit is equipped with two sensors T1_indoor & T2_outdoor. Sensors indoor sensor (NTC 12k@25°C β=3740) This sensor measures the returned air temperature from the room outdoor sensor (NTC 12k@25°C β=3740)
JAKKA Control Kit 4 Manual 2.1 Control modes The control mode can be changed by pressing the MODE button (one or multiple times) on the 186RC. The following operational modes can be selected: COOL HEAT AUTO ...
JAKKA Control Kit 4 Manual 2.1.3 Mode 3: HEAT During the summer season the HEAT mode either can be manually selected with the remote control or automatically controlled via the BMS (Building Management System) inputs When BMS J5(5-13) is ON (closed) and season select input J5(1-9) is open, the mode will be HEAT.
JAKKA Control Kit 4 Manual 2.1.4 Mode 4: AUTO In the auto mode the control selects automatically, dependent on the outdoor temperature, if it is summer or winter season. In accordance with the selected season the unit will work in cool or heat mode as described in previous paragraphs.
JAKKA Control Kit 4 Manual 2.4.4 Working with Modbus The Modbus communication goes from the Main (MN) board, MN is slave. The data goes from MN to the Remote Control (RC) with communication protocol Senso Argus link. The RC is master and the MN is slave. The Modbus is 8 times faster as the Senso Argus Link communication.
JAKKA Control Kit 4 Manual 2.4.5 Example Read Read bits Parameter Default Range Write Write disable Errors 0-126 Temp -30-80 Bytes Description Bits # slave 0000.0001 commando 0000.0003 start addr H 0000.0000 start addr L 0000.0005 # data H WEEE.EEEE # data L TTTT.TTTT...
JAKKA Control Kit 4 Manual SUPPLY FAN EXHAUST FAN SUPPLY FAN EXHAUST FAN OFFSET OFFSET Negative Offset Positive Offset Supply Fan is adjusted because the limit of the fan MAX and MIN is reaches. Negative Offset is Supply Fan LOW = Exhaust Fan + Offset...
JAKKA Control Kit 4 Manual 3 Remote Control MON TUE WED THU FRI SAT MODE SET TEMP 12.00 º C HIGH COOL HEAT AUTO EXHAUST FAN SUPPLY FAN BY – FILTER PASS CHECK RUN/STOP MODE FAN SPEED TIMER RESET SCHEDULE SELECT The buttons and display have a short description.
JAKKA Control Kit 4 Manual 3.1.1 LCD functions Shows Actual time or Actual room temp Only visible when When blinking current day timer blocks or set point changing fan speed Timer is active MODE SET TEMP MON TUE WED THU FRI SAT SUN º...
JAKKA Control Kit 4 Manual Additional features A specific “on” or “off” time can be deleted by pressing RESET when programming the time block. If deleted the time display shows: and the time is not used. When for example the unit is “on” on Monday and no “off” time is programmed that day anymore, the unit remains “on”...
JAKKA Control Kit 4 Manual 3.1.4 Errors In the figure you can see what errors are displayed on the remote control. When there are errors the remote control switch off the heat recovery unit. No error No Error Heating control...
JAKKA Control Kit 4 Manual 4 Labvision With Labvision the system can be tested and programmed. Application Labvision runs on PC. PC is connected Senso Argus USB mouse to the Senso Argus Link. For each board and functions are project defined.
Page 18
JAKKA Control Kit 4 Manual 4.2 RC This project shows all E2prom variables and variables that are set when the Remote Control is running. By pointing at a red label the variable can be changed. www.jakkagroup.com...
Page 19
JAKKA Control Kit 4 Manual 4.3 MN This project shows variables that are set when the Main Controller is running. The buttons can be pushed to change a variable. Each connector on the board has a color to see where the variable is connected physically.
JAKKA Control Kit 4 Manual 4.4 MN/RC modbus This project shows variables that are set when the Main Controller is connected with Remote control and modbus. The information on the screen are divided in several items: 1. Read buffer in MN has the data which reads by Modbus master.
JAKKA Control Kit 4 Manual 5 System Test If the software is changed we do several tests to make sure the software is correct. Test the different modes of the system: 1. MODBUS 2. BMS 3. RC 4. ERROR 5. MODE HEATER 6.
JAKKA Control Kit 4 Manual 5.1.2 Modbus tester production 06 The table has A to Q commando’s for the Modbus tool. Check all commando’s in labvison screen. By step I in table the display is off but the fans are on for cooling the heaters. In the first table we test the Purge time, run, mode, master Modbus, exhaust fan, supply fan, set point degrees.
JAKKA Control Kit 4 Manual 5.1.3 Labvision This is the final screen after the test. 5.2 BMS BMS is Building Manage System connected with 3 lines BMS, Unit, Season. Labvision is used to check if all variables are correct project F2 MN. Follow points to test the BMS. Which heater are on with difference of Set Point Room or Indoor sensor.
JAKKA Control Kit 4 Manual 5.3 RC RC will be test the system with use of the buttons. Follow points to test the RC. Push Result UNIT button None None ON/OFF ON/OFF LED on, fan speed can be changed ON/OFF...
JAKKA Control Kit 4 Manual 5.8 Mode COOL Several conditions in described in paragraph 2.1.2. Test the bypass valve. If Bypass valve is open there is a hysteresis of 1 degrees to close the Bypass valve. T1<T2 T1>T3 T2< T2>...
JAKKA Control Kit 4 Manual 5.12 Weekly Timer Weekly Timer works only when no BMS or Modbus is connected. To activate the Weekly Timer press button RUN/STOP. RC is on, led is on. Press Timer button and immediately button mode for 3 seconds.
JAKKA Control Kit 4 Manual 6 Connections to the Senso Argus 186 main board 6.1 PCB layout In following print layout, the connectors and components are visualized. ° www.jakkagroup.com...
JAKKA Control Kit 4 Manual 6.2 Connection diagram J9-2 Heating Element Power 12 - Volt J16-1 J9-5 Relay 1 230VAC Powe r 12 + Volt J16-5 J9-3 Heating Element 0-10 - Volt J16-2 J9-6 Relay 2 230VAC 0-10 + Volt...
JAKKA Control Kit 4 Manual 6.3 Connector description Connector Pin Description Earth (Stelvio, BS95/4A + CT84) 230V neutral (Stocko, MKF 2800 series) 230V phase The control is equipped with one fuse, in the phase. The Mains input fuse-holder is appropriate for glass fusses of 5x20 mm. The control is default equipped with one TBD slow fuse.
Page 30
JAKKA Control Kit 4 Manual Connector Pin Description Earth (Stelvio, BS95/7A + CT84) Output heating element relay #1 (230VAC) (Stocko, MKF 2800 series) Output heating element relay #1 (230VAC) Output heating element relay #1 (230VAC) Heating outputs Usable output current is TBD.
Page 31
JAK-KA GROUP - SRBIJA adresa: Bulevar Zorana Đinđića 80 11070 Novi Beograd, Srbija telefon: +381 (0)11 2 600 901 faks: +381 (0)11 2 600 906 web: www.jakkagroup.com e-mail: jakkagroup@jakkagroup.com JAK-KA GROUP - CRNA GORA adresa: V Crnogorske brigade 3 85347 Igalo, Crna Gora telefon: +382 (0)31 330 285 faks: +382 (0)31 330 285 mobilni: +382 (0)69 517 008...