WARNING
SHOCK HAZARD! Turn off
electrical power at circuit breaker,
use voltmeter or circuit tester to
ensure that POWER IS OFF.
DC
ok
DC ok
2 2 2 4 4 4 7 10 11 12 15 M1 M2 M3 T1 T2 T3
Adjust
Power Supply
INPUT
N
N
6
2 GPM
5 GPM
SOLENOID
SOLENOID
grind2energy.com
Wiring Connections
Incoming power supply requires that:
•
Ground wire is securely fastened to
panel as shown.
•
208-230V system use #8 AWG wire
from line disconnect switch and control
box.
•
460V system use #12 AWG wire from
line disconnect switch to control box.
L1
L2
L3
1 ON
L1
L2
L3
Control Box
2 2 2 4 4 4 7 10 11 12 15 M1 M2 M3 T1 T2 T3
5
4
FLOAT
PRESSURE
SWITCH
DC ok
Adjust
Power Supply
INPUT
N
3
2
GRINDER
SWITCH
Grind2Energy Technical Support: 844-874-7529
Grind2Energy
™
Wiring Connections
The pump lead wires are connected to
1
"T1, T2 & T3" as shown below.
The grinder lead wires are connected
2
to "M1, M2 & M3" as shown below.
The pressure switch leads are con-
3
nected to the control panel as shown
below (black to black, brown to brown,
blue to blue).
The lead wire for the tank float switch
4
is connected to terminal connections 2
and 15 as shown below. This wire runs
along the length of the discharge line
to the tank.
The 5gpm solenoid valve lead wires
5
are connected to terminal 11 & 12 as
shown below.
The 2gpm solenoid valve lead wires are
6
connected to terminal 7 & 10 as shown
below.
DC
ok
L1
L2
L3
1 ON
L1
L2
L3
N
17
1
INCOMING
PUMP
POWER
G2E015-15F-89-84
System
| 8